Caution, Wiring – Honeywell C7046A User Manual

Page 2

Advertising
background image

C7046A,B,C,D AIR TEMPERATURE SENSORS

62-0216

2

Fig. 2. Mounting C7046 Air Temperature

Sensor on a flat duct or plenum surface.

Fig. 3. Mounting C7046 Air Temperature

Sensor in a junction box.

Wiring

CAUTION

Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.

CAUTION

Erratic System Operation Hazard.
Failure to follow proper wiring practices can
introduce disruptive electrical interference
(noise).

Keep wiring at least one foot away from large

inductive loads such as motors line starters,
lighting ballasts, and large power distribution
panels.

Shielded cable is required in installations where

these guidelines cannot be met.

Ground shield only to grounded controller case.

IMPORTANT

1. All wiring must agree with applicable codes,

ordinances and regulations.

2. Do not mount sensor in incorrect environment.
3. Wire according to the applicable controller

instructions.

4. Erratic temperature readings from a sensor can

be caused by improper wiring practices. These
must be avoided to assure proper operation:
•Avoid poor wiring connections.
•Avoid intermittent or missing building earth

ground.

•Do not mount sensor in incorrect environment.

Connect low voltage wiring from the sensor to the
appropriate system component terminals using
solderless connectors. See Fig. 3.

NOTES:

1.

For connections to the W973 Single Zone
Logic Panel, see Fig. 4.

2.

For connections to the W7080 Multizone
System, see Fig. 5.

3.

For connections to the Excel 500 Control
System, see Fig. 6.

4.

For additional wiring information, refer to the
appropriate specification.

Fig. 4. Connecting C7046A Air Temperature

Sensor to a W973 Single Zone Logic Panel.

SENSOR
PROBE

SYSTEM DUCT
OR PLENUM

FLANGE

NO. 8 (4mm)
MOUNTING SCREWS
(NOT PROVIDED)

TO

APPROPRIATE

SYSTEM

COMPONENTS

CONNECT SENSOR

WIRES WITH TWO

WIRENUT CONNECTORS

(NOT PROVIDED)

M22403A

SENSOR

PROBE

SYSTEM

DUCT OR

PLENUM

FLANGE

STANDARD UTILITY

CONDUIT BOX

CONNECTOR

LOCKNUT

AND

CONDUIT

BLANK

FACEPLATE

(OPTIONAL)

TO APPROPRIATE

SYSTEM

COMPONENTS

CONNECT SENSOR WIRES

WITH TWO WIRENUT

CONNECTORS (NOT PROVIDED)

M22404A

NO. 8 (4 mm)

MOUNTING

SCREWS (NOT

PROVIDED)

R

T

T1 3

4

2

5

1 T RT R W B Y

R

SENSOR

STAT

24 VAC

ECONO

C +20 H N

1

C7046A

L1
(HOT)

L2

W973 LOGIC PANEL

M17965

1

POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.