S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

26

Pump Configuration Parameters

Table 17 displays Pump configuration parameters. Use the left

and right arrows to switch between Central Heat, Boiler, DHW,

System, Auxiliary 1, and Auxiliary 2 pumps. The parameters

are the same for all pumps.

Pressing the Advanced Settings button brings up a number of

other advanced configuration options for each pump. Press the

Control Settings button to return to the screen shown in Fig.

45.

Fig. 45. Pump configuration.

*Table 61 on page 53 has more parameters listed.

NOTE: The R7911 Steam Control does not have pumps, but

the outputs are available to operate air dampers or

accessories. CH Pump, Boiler Pump and System

Pump are used for these output options.

Table 17. Pump Configuration Parameters for

R7910A Hydronic System.

Parameter

Comment

Pump control

Auto

On

Pump output

Pump A

Pump B

Pump C

None

Pump start delay

___hour ___min ___sec

Overrun time

___hour ___min ___sec

Table 17a. Pump Configuration Parameters for R7911

Steam Modulation Configuration Parameters.

Parameter

Comment

Auxiliary pump control

Auto

On

Auxiliary pump is on when

CH pump is ON

Slave command

Auxiliary pump output

Pump A

Pump B

Pump C

None

Boiler pump control

Auto

On

Boiler pump output

Pump A

Pump B

Pump C

None

Boiler pump overrun time

0-600 seconds

0 = Not configured

CH pump control

Auto

On

CH pump output

Pump A

Pump B

Pump C

None

CH pump overrun time

0-600 seconds

0 = Not configured

System pump control

Auto

On

System pump output

Pump A

Pump B

Pump C

None

System pump ourrun time

0-600 seconds

0 = Not configured

Pump exercise time

0-600 seconds

0= Not configured