S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

33

65-0303—05

After successful login, the user presses the Begin button to

start safety parameter verification. See Fig. 59.

Fig. 59. Begin safety verification.

The first group of safety configuration parameters that needs

verification is displayed. The user is asked to confirm that the

settings are correct, as shown in Fig. 60.

Fig. 60. Confirm safety parameter settings.

After the first safety parameter group has been confirmed by

the user (by pressing the Yes button), the next safety

parameter group waits for verification as shown in Fig. 61.

Fig. 61. Safety parameter settings confirmed; next group

waiting for confirmation.

The user has 30 secs to confirm each safety configuration

group’s settings. If the user takes too long to confirm the

settings, an error message is displayed, as shown in Fig. 62.

Fig. 62. Confirmation timed out.

After all safety parameter groups have been verified, the user

must press the Reset button on the control within 30 seconds

to confirm the correct device. See Fig. 63.