S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

36

Lead Lag Slave Configuration
Parameters (Hydronic Control Only)

Table 34 displays Lead Lag Slave Configuration parameters.

Fig. 68. Lead Lag slave configuration.

Lead Lag Master Configuration
Parameters (Hydronic Control Only)

Table 35 displays Lead Lag Master Configuration parameters.

Click the Advanced Settings button to see available advanced

parameters as shown in Table 36–44.

Use the left and right arrows to switch between Modulation,

CH, DHW, Frost Protection, Warm Weather Shutdown,

Algorithms, Rate Allocation, Add stage and Drop stage

parameters.

Fig. 69. Lead Lag master configuration and Advanced

Settings button.

Table 34. Lead Lag Slave

Configuration Parameters.

Parameter

Comment

Slave enable

Slave

ModBUS slave

Disabled

Slave mode

Use first

Use last

Equalize run time

Base load rate

0–6000 rpm

Slave sequence

order

0–8

Demand to firing

delay

___hour ___min ___sec

Fan rate during off

cycle

0–12000 rpm

ModBus port

MB1

MB2

No port

ModBus address

0–250

Table 35. Lead Lag Master Configuration Parameters.

Parameter

Comment

Master enable

Enabled

Disabled

CH setpoint

-40 °F to 266 °F (-40 °C to 130 °C)

CH time of day

setpoint

-40 °F to 266 °F (-40 °C to 130 °C)

ModBus port

MB1

MB2

No port

ModBus address

1–250

Table 36. Lead Lag Master Configuration

Advanced Settings: Modulation Parameters.

Parameter

Comment

Modulation backup

sensor

Lead outlet sensor

Slave outlet sensor average

Disabled

Off hysteresis

0 °F to 234 °F

(-17 °C to 112 °C)

On hysteresis

0 °F to 234 °F

(-17 °C to 112 °C)

Hysteresis step time ___Hour ____Minute _____Second
P gain

0 - 400

I gain

0 - 400

D gain

0 - 400