Diagnostics, Date and time, Trend analysis snapshot – Honeywell Local Operator Interface S7999B User Manual

Page 51

Advertising
background image

51

65-0303—05

• Setpoint (for corresponding demand source)

• Burner firing rate

• Hysteresis on (for corresponding demand source)

• Hysteresis off (for corresponding demand source)

The Clear button is disabled for the PID analysis (doesn’t apply to

hysteresis).

The default sample rate is 15 sec periods (a tick mark on the X axis

for every 15 second period, with minutes displayed every 4 tick

marks).

Special case trend analysis graph for R7910/R7911 vessel heat

exchange can be selected.

Fig. 112. Vessel analysis page.

Data included in the vessel analysis graph are:

• Outlet temperature

• Inlet temperature

• Heat exchange (outlet – inlet)

• Burner firing rate

Automatic sampling of trend data takes place when the trend

analysis report is displayed. No user intervention is necessary to

invoke sampling.

NOTE: Sample data is collected and stored in the S7999B. The

R7910 or R7911 don’t collect any historical data for trending

purposes. For this reason any S7999B reset causes all

R7910 or R7911 sampling to start over with no data.

Trend analysis of the following data from each R7910/R7911 is

possible:

Trend Analysis Snapshot

The trend analysis snapshot file is stored in Comma Separated Value

(CSV) format in the S7999B so it can be imported into a spreadsheet

program such as Microsoft Excel.

The trend analysis snapshot file can be viewed in graph form on the

S7999B. It is also accessible in an Ethernet FTP session with the

S7999B. This FTP session can be used to export the trend analysis

snapshot file from the S7999B.

Diagnostics

Pressing the Diagnostics button permits some display hardware

diagnostics (see Fig. 104). Normally, these diagnostics are

applicable only for factory testing purposes, but conditions may

arise that warrant this testing.

Fig. 113. Display diagnostics.

NOTE: COM 1 Communication test is a factory-only test. Perform-

ing this text when not connected to a factory test fixture will

always yield a “Failed” result.

Each test is invoked by pressing the Test button next to the

diagnostic. The results of the diagnostic test (“PASS” or “FAIL”)

display in the text box next to the Test button.

Date and Time

Display time can be configured in the S7999B and S7999C OI

Displays and applied to the R7910A or R7911. A date and time is

entered by the user at the display and any data that is timestamped is

marked with the current time and date in the display.

Table 59. R7910/R7911 Trend Analysis Data.

Data

Comment

Demand source

CH, DHW, LL (Lead Lag), or

FP (Frost Protection) Steam

Sensor

Outlet temperature (R7910

only)
Firing rate

% or RPM

Fan speed

PWM feedback

Flame signal strength

V

Inlet temperature (R7910

only)

If enabled

DHW temperature (R7910

only)

If enabled

Outdoor temperature

If enabled

Stack temperature

If enabled

Header temperature (R7910

only)

If enabled

CH setpoint

Actual CH setpoint based on

time of day (TOD).

DHW setpoint (R7910 only)

Actual DHW setpoint based

on TOD.

Central Heat Operation

Analysis
Domestic Hot Water

Operation Analysis (R7910

only)
Vessel Analysis

Table 59. R7910/R7911 Trend Analysis Data. (Continued)

Data

Comment