Honeywell Local Operator Interface S7999B User Manual

Page 55

Advertising
background image

55

65-0303—05

DHW enable Disable or Enable Domestic Hot

Water Loop

11

23

DHW

demand

switch

Sensor for Central Heat

demand:

DHW sensor only,

DHW sensor & Remote Stat,

DHW switch & inlet sensor, or

DHW switch & outlet sensor

DHW Priority

source

Which system has priority:

Disabled or

Heat Demand

DHW Priority

method

Boost during priority time

Drop after priority time

DHW

Modulation

sensor

DHW Sensor

Outlet Sensor

Inlet Sensor

Auto: DHW (S6) or Inlet Sensor

Auto: DHW (S6) or Outlet

Sensor

DHW

setpoint

-40 °F to 240 °F

(-40 °C to 115 °C)

DHW time of

day setpoint

Setpoint when Time Of Day

switch is on. -40 °F to 240 °F

(-40 °C to 115 °C)

DHW off

hysteresis

Differential above setpoint

when boiler is turned off. -40 °F

to 240 °F (-40 °C to 115 °C)

DHW on

hysteresis

Differential from setpoint when

boiler is turned on. 2 °F to

234 °F (-16 °C to 112 °C)

DHW priority

override time

___hour ___min ___sec

DHW

hysteresis

step time

Time between hysteresis step

changes: 0-600 seconds

(0=Disable hysteresis stepping)

DHW priority

vs CH

Which system has priority:

Central Heat over Domestic Hot

Water, or

Domestic Hot Water over

Central Heat

DHW priority

vs LL

Which system has priority:

Lead Lag over Domestic Hot

Water,

Domestic Hot Water over Lead

Lag

DHW P-gain Time between hysteresis step

changes: 0-400

DHW I-gain

Time between hysteresis step

changes: 0-400

DHW D-gain Time between hysteresis step

changes: 0-400

DHW storage

enable

Enabled, Disabled

12

23

Storage time ___hour ___min ___sec
Setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Off

hysteresis

-0 °F to 180 °F (-17 °C to 82 °C)

On

hysteresis

-0 °F to 180 °F (-17 °C to 82 °C)

Table 61. Configurable Parameters. (Continued)

Parameter

Comment

Table

#

Page

#

Tap detect

degrees

-0 °F to 180 °F (-17 °C to 82 °C) 13

23

Tap detect on

recognition

time

___hour ___min ___sec

Tap detect on

threshold

-0 °F to 180 °F (-17 °C to 82 °C)

Tap detect

minimum on

time

___hour ___min ___sec

Tap stop

inlet-DHW

degrees

-0 °F to 180 °F (-17 °C to 82 °C)

Tap stop

outlet-Inlet

degrees

-0 °F to 180 °F (-17 °C to 82 °C)

Plate preheat

setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Plate preheat

on

recognition

time

___hour ___min ___sec

Plate preheat

on hysteresis

-0 °F to 180 °F (-17 °C to 82 °C)

Plate preheat

off hysteresis

-0 °F to 180 °F (-17 °C to 82 °C)

Plate preheat

detect on

threshold

-0 °F to 180 °F (-17 °C to 82 °C)

Plate preheat

detect off

threshold

-0 °F to 180 °F (-17 °C to 82 °C)

Plate preheat

minimum on

time

___hour ___min ___sec

Plate preheat

delay after

tap

___hour ___min ___sec

Warm

Weather

Setpoint

Enable

Enabled, disabled

14

24

Warm

Weather

Setpoint

-40 °F to 266 °F

(-40 °C to 130 °C)

Table 61. Configurable Parameters. (Continued)

Parameter

Comment

Table

#

Page

#