S9360A, S9361A, S9370A, S9371A INTEGRATED BOILER CONTROLLERS

13

69-2076—01

Fig. 10. Operating Sequence.

IGNITION

SEQUENCE

IDLE

ALL OUTPUTS OFF

CHECK LEAKAGE/

SET FLAME BIAS

WAIT LIMIT

SWITCH CLOSE

CHECK DAMPER/

PRESSURE SWITCH

OPEN

DRIVE DAMPER/

INDUCER WAIT FOR

SWITCH CLOSE

PREPURGE

SPARK

TURN PILOT VALVE ON

CHECK FLAME

PRE-TRIAL

SOFT LOCKOUT

PROVE FLAME

STOP SPARKING

FLAME STABILIZATION

TURN MAIN VALVE ON

RUN

POSTPURGE

WATER TEMPERATURE LOW AND THERMOSTAT ACTIVE

BIAS DONE

WATER TEMP.

HIGH OR CALL

FOR HEAT LOST

SWITCH OPEN

SWITCH CLOSE

SWITCH OPEN

FLAME DEB ON

FLAME DEB OFF

TIME OUT

TIME OUT OR

MANUAL RESET

LIMIT SWITCH

OPEN

TIME OUT

FLAME SENSED

FLAME PROVED

TIME OUT

WATER TEMPERATURE HIGH OR THERMOSTAT CALL FOR HEAT LOST

RETRY DELAY

TIME OUT

A

TIME OUT

RECYCLE DELAY

DAMPER/

PRESSURE

SWITCH OPEN

CHECK FLAME

POST-TRIAL

FLAME DEB ON

FLAME DEB OFF

FLAME LOST

A

TIME OUT

A

TIME OUT

TIME OUT

B

B

CIRCULATOR ON

CIRCULATOR OFF

THERMOSTAT CALL FOR HEAT LOST

IDLE

ALL OUTPUTS OFF

THERMOSTAT CALL FOR HEAT ACTIVE

CIRCULATOR

CONTROL

M27073

LIMIT SWITCH CLOSE