EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

95-7520—02

10

NOTE: The node can be reset by switching the node to MANUAL and then switching to the normal operating mode

(using DestManMode).

Also, the Excel 10 network variables, AlarmLogX, where X is 1 through 5, that store the last five alarms to occur in the

controller, are available. These points can be viewed through XBS, XI584 or E-Vision.

Table 1. Excel 10 Alarms.

Name of alarm or error bit

Alarm type

number

NO_ALARM

0

No alarms presently detected.

INPUT_NV_FAILURE

1

One or more NV inputs have failed while receiving an update within their

specified FAILURE_DETECT_TIME.

NODE_DISABLED

2

The control algorithm stopped because the controller is in DISABLED_MODE,

or FACTORY_TEST mode. The control is shut down and disabled until power is

cycled or the node is reset. See NOTE 1 below.

SENSOR_FAILURE

3

One or more sensors have failed.

FROST_PROTECTION_ALARM 4

The space temperature is below the frost alarm limit 42.8

°

F (6

°

C) when the

mode is FREEZE_PROTECT. The alarm condition remains until the

temperature exceeds the alarm limit plus hysteresis.

INVALID_SET_POINT

5

One of the Setpoints is not in the valid range.

LOSS_OF_AIR_FLOW

6

The Fan Status DI indicates that there is no air flow when the node is

commanding the fan to run. The control is shut down and disabled until power is

cycled or the node is reset. The alarm is not issued until FanFailTime seconds

have elapsed since the loss-of-flow condition was first reported.

DIRTY_FILTER

7

The pressure drop across the filter exceeds the limit and the filter requires

maintenance. The control runs normally.

SMOKE_ALARM

8

The smoke detector has detected smoke and the node has entered an

emergency state.

IAQ_OVERRIDE

9

The indoor air quality sensor has detected that the indoor air quality is poorer

than the desired standard and additional outdoor air is being brought into the

conditioned space.

LOW_LIM_ECON_CLOSE

10

The economizer has to close beyond the minimum position to prevent the

discharge air temperature from going below the discharge temperature low

limit.

DRIP_PAN_FULL

11

Drip pan maintenance is required. Cooling control is disabled. Fan continues to

run.

FREEZE_STAT

12

Very Cold Temperature detected inside the Unit Ventilator Cabinet. Control

closes OA Damper, and open heat valve.

OAQ_ALARM

13

The configured outdoor air quality sensor has detected CO or CO

2

levels that

exceeds OaQStPt (plus 30 ppm hysteresis). When there is an OAQ_ALARM,

the economizer damper is closed.

RETURN_TO_NORMAL

128

Return to no alarm after being in an alarm condition. This code is added

numerically to another alarm code to indicate that the alarm condition has

returned to normal.

ALARM_NOTIFY_DISABLED

255

The alarm reporting was turned off by the nviManualMode. No more alarms are

reported until nviManualMode turns on alarm reporting or upon application

restart.