EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

9

95-7520—02

Verify Termination Module Placement

The installation wiring diagrams should indicate the locations

for placement of 209541B Termination Module(s). Refer to the

E-Bus Wiring Guidelines, form 74-2865, and the Excel 10 FTT

Termination Module Installation Instructions, form 95-7554.

Correct placement of the termination module(s) is required for

proper E-Bus communications.

Step 2. Startup

W7753A CONTROLLER STATUS LED
The LED on the front and center of a W7753A Controller

provides a visual indication of the status of the controller. See

Fig. 15. When the W7753A receives power, the LED should

appear in one of the following allowable states:

1. Off—no power to the processor.

2. Continuous On—processor is in initialized state.

3. Slow Blink—controlling, normal state.

4. Fast Blink—when the Excel 10 has an alarm condition.

Fig. 15. LED location on W7753A.

ALARMS
When an Excel 10 has an alarm condition, it reports it to the

central node on the E-Bus (typically, the Excel 10 Zone

Manager, or Small Building Controller). See Table 1. The

information contained in an alarm message follows:

• Subnet Number: This is the E-Bus subnet that contains the

Excel 10 node that has the alarm condition. Subnet 1 is on

the Zone Manager side of the router; Subnet 2 is on the

other side of the router.

• Node Number: This is the Excel 10 node that has the alarm

condition (see Network Statics).

Alarm Type: The specific alarm being issued. An Excel 10 can

provide the alarm types listed in Table 1.

Broadcasting the Service Message

The Service Message allows a device on the E-Bus to be

positively identified. The Service Message contains the

controller ID number and, therefore, can be used to confirm

the physical location of a particular Excel 10 in a building.

There is one method of broadcasting the Service Message

from an Excel 10 W7753A Controller. This uses a hardware

push button on the side of the controller (see Fig. 16).

When an Assign ID command is issued from the

commissioning tool, the node goes into the

SERVICE_MESSAGE mode for five minutes. In the

SERVICE_MESSAGE mode, pressing the service pin on the

controller or the bypass button on a wall module causes the

Service Message to be broadcast on the network. All other

functions are normal in the SERVICE_MESSAGE mode.

Step 3. I/O Tests

The controller must be configured using the Excel 10 E-Vision

PC configuration tool. Once this is done, the W7753A can be

commanded to MANUAL mode, and each output can be

exercised/viewed to verify proper wiring connections and

equipment operation. See the Excel 10 E-Vision Users Guide,

form 74-2588 for details on configuring and testing W7753A

Controllers.

Fig. 16. Location of the service pin button.

Step 4. Verify Sequences of Operation

For the detailed descriptions of the sequences of operation,

see the Excel 10 Unit Ventilator System Engineering,

form 74-2964 Appendix B.

M12697

1

2

3

4

5

6

7

8

9 10 11 12 13 14

15 J3

31 30 29 28 27 26

25 24 23 22 21 20

19 18 17

16

E

GND

LED BYPASS SNSR GND SET PT AI-1

OHM

GND A1-2

OHM

AI-3

V/mA

GND AI-4

V/mA

22VDC

OUT

E-BUS E-BUS

JACK

DI-4 GND DI-3 DI-2 GND

DI-1 24

VAC

24

VAC

COM

1

OUT

2

OUT

3

OUT

4

OUT

5

OUT

6

OUT

7

OUT

8

OUT

W7753A

STATUS

LED

M10094

SERVICE
PIN
BUTTON