SUB SERIES INTERVAL DATA RECORDERS

11

62-0342—01

Fig. 15. Hard-wiring the SUBIDR-16.

SUBIDR-16, Using Other Utility-Type Meters

(Gas, W ater , Etc.)

Up to 16 Meters

Up to 16 Meters

Channel 2

~

~

~

~

Channel 1

Channel 3

Up to 4000 F eet T otal

Up to 4000 F eet T otal

Up to 26

SUBIDR-16’s

Up to 26

SUBIDR-16’s

NO TE: Meter s m ust be installed within 500 f eet of IDR.

Meter connected with a pair of #22-#14 A WG conductors.

A C Adapter

SUB-RS232K*

6' cab le pro vided b y

Honeywell (15 ft max.)

RS-232 Ser ial P or t

COM1 - COM4

Up to 16 Meters

Up to 16 Meters

SUBIDR-16, Using Honeywell

Meters

Up to 16 Meters

Up to 16 Meters

Channel 2

~

~

~

~

Channel 1

Channel 3

Up to 4000 F eet T otal

Up to 4000 F eet T otal

Up to 26

SUBIDR-16’s

Up to 26

SUBIDR-16’s

NO TE: Meter #1 m ust be installed within 100 f eet of IDR.

Meter s #2-#16 m ust be installed within 500 f eet of IDR.

Meter #1 uses 8-conductor cab le.

Meter s #2-16 use 6-conductor cab le.

A C Adapter

SUB-RS232K*

6' cab le pro vided b y

Honeywell (15 ft max.)

RS-232 Ser ial P or t

COM1 - COM4

PC

Up to 16 Meters

Up to 16 Meters

A C Adapter

A C Adapter

A C Adapter

A C Adapter

IDR

IDR

IDR

IDR

IDR

IDR

IDR

IDR

PC