removed. The third-party meter IDR uses a DIP switch to

perform this function. This switch is preset at the factory and

requires no further adjustment.

Fig. 5. Overview of main circuit board.

MAIN CIRCUIT BOARD VISUAL
CHECKS

Once you have connected meter #1 to jack #1 in the IDR, the

IDR should be energized. If the IDR is not energized, verify:

1. Meter #1 is turned on. (Meter #1 powers the IDR; if

Meter #1 is not installed and powered up, the IDR will

not function.)

2. Verify that JMP8 on the IDR circuit board has a jumper

installed.

3. Verify that J23 & J24 on the IDR circuit board are set in

the position labeled “MTR”. Both jumpers should be set

to the RIGHT position.

4. Verify that the cable between Meter #1 and Jack #1 on

the IDR is properly assembled. (See Appendix A for

cable assembly.)

NOTE: If the IDR is being powered by the optional AC

adapter instead of by Meter #1, see Section 5.0.

Verify the status of the LED indicators on the IDR circuit

board. (See Appendix B for locations.)

1. Power Supply Indicators

L3, green -> This LED is ON.

L1, green -> This LED is ON.

2. System status indicators

D4 (CPU), red -> This LED flashes once per sec-

ond. If D4 flashes twice per second, the IDR is not

initialized. This will be addressed later using E-

Mon Energy software.

D7 (Low Battery) -> This LED must be OFF. This

LED indicates a low or missing battery.

D6 (System Error) -> This LED must be OFF.

3. Meter pulse indicators

Yellow LEDs P1 through P8 may be flashing.

These LEDs indicate each meter’s pulse rate.

The flash rate depends on how much load the

meter is measuring. The faster the pulse the

greater the load.

IMPORTANT:

IF THE METER MEASURES ZERO LOAD, THERE

IS NO METER PULSE, WHEN THE PULSE RATE

IS ZERO THE YELLOW LED INDICATOR WILL

REMAIN EITHER ON OR OFF UNTIL THERE IS A

LOAD.

NOTE: If one of the LEDs does not flash, verify the meter

connection first. If the meter is properly connected,

check the meter’s display for a flashing load indica-

tor.

4. Panel Indicators

Two LEDs are visible through the window on the

door of the stand-alone enclosure. THESE LEDS

ARE NOT PRESENT IN MMU STYLE IDRS.

Green LED (Power Indicator) -> The green LED

indicates that power is present at the IDR.

Red LED (Tamper Alarm) -> The red LED indi-

cates that the IDR door has been opened. This

tamper alarm LED will be on when the door is

closed, and will flash when the door is open.

When the software startup is performed, the IDR

will be initialized by the E-Mon Energy software

and the alarm LED will turn off as long as the door

remains closed. The alarm can only be reset

through the software.

5. IDR 16 Option 16 Card (applies only to the SUBIDR-16

model.)

For each meter (9-16) installed on the options

card, another set of yellow LEDs (P9-P16) will be

present. These LEDs indicate the meter pulse

rate for meters #9 through #16.

OPTIONAL AC ADAPTER
(OPTIONAL EXTERNAL 120 VAC
POWER SUPPLY)

If you are NOT using the optional AC adapter to power the

IDR, proceed to Section 6.0.

Instead of powering the IDR using Meter #1, Honeywell can

supply an optional AC adapter. If the IDR was provided with

this option, verify the following:

1. Jumpers J23 & J24 on the IDR circuit board are set to

the LEFT position (position labeled “EXT”.)

2. Jumper at JMP8 MUST be removed.

3. The AC adapter’s two-wire cord must be plugged into

the IDR at TB9. (The polarity of these wires does not

matter.)

4. Plug the AC adapter into a 120 VAC outlet.