APPENDIX D - SYSTEM WIRING GUIDES

Fig. 12. Wiring overview for SUBIDR-8.

Note: Meter 1 must be installed within
100 feet of IDR. Meters 2-8 must be installed
within 500 feet of IDR.

(Up to 8 Meters)

(One of three channels shown for clarity.)

(Up to 8 Meters)

~

~

Channel 1 of 3

4-Conductor

Flat Modular Cable

Up to 4000 Feet Total

Daisy-Chain or

Star Connection

Up to 52 SUBIDR-8s per channel

AC Adapter

SUB-RS232K

6' cable provided by

Honeywell

(15 ft max.)

8-conductor cable

& modular plug

DB-9 (DTE) Connector

PC

RJ-45

RJ-11

8-Cond.

RJ-45

RJ-11

6-Cond.

RJ-45

6-Cond.

RJ-45

Wiring Guide for SUBIDR-8

IDR A

IDR Z

CONNECTION CABLE

TYPE CONNECTOR

SUBIDR to Honeywell Meter #1

8-cond. 22-26 AWG

RJ-45

flat

modular

cable

SUBIDR to Honeywell Meters #2-8

6-cond. 22-26 AWG

RJ-45

(Pins 1 & 8 not used)

SUBIDR to SUBIDR

4-cond. 26 AWG

RJ-11

SUBIDR to SUB-RS232K

4-cond. 26 AWG

RJ-11

SUB-RS232K to Computer *

8-cond. 22-26 AWG

RJ-45/DTE

flat

modular

cable

SUB-RS232K to Modem *

8-cond. 22-26 AWG

RJ-45

flat

modular

cable

SUBIDR to SUB-USBK *

Allows connection directly

to

the

computer

USB

SUBIDR to Pulse Meter

2-cond. 14-22 AWG

* Supplied by Honeywell

Note: When constructing field-installed cables, modular cables must be made
so that the individual wires go through on the same pin number.