Section 8: finishing, Finishing, Warning – Heat & Glo Fireplace HEAT & GLO TWILIGHT-II User Manual

Page 18

Advertising
background image

Heat & Glo LifeStyle Collection • Twilight-II • 2087-900 Rev. G • 12/05

18

A. Mantel Projections

Figure 8.1 shows the minimum vertical and corresponding
maximum horizontal dimensions of appliance mantels or
other combustible projections above the top front edge of
the appliance.

Finishing

8

Figure 8.2 Clearances to
Combustible Mantel Leg or
Wall Projections (Acceptable
on both sides of opening.)

Figure 8.1 Indoor Clearances to Mantels or other
Combustibles above Appliance

12

11

10

9

8

7

6

13-5/8

12-5/8

11-5/8

10-5/8

9-5/8

8-5/8

7-5/8

HOOD

NON-COMBUSTIBLE BOARD

(SUPPLIED ON APPLIANCE)

Note: Measurements

are in inches.

Interior
V i e w

MEASURED

FROM CORNER

FIREPLACE

HOOD

½ IN.

TOP VIEW

B. Facing Material

Fire Risk.

Do NOT obstruct air inlet or outlet grilles.

Do NOT modify grilles.

Modifying or covering grilles could cause

temperature rise and fire hazard.

WARNING

Finishing materials must not interfere with:

Air flow through grilles or louvers.

Operation of louvers or doors.

Access for service.

Inside Facing Material

May install combustible materials up to specified
clearances on top, front and sides of appliance.

Seal joints between finished wall and appliance top and
sides with 300

0

F (140

0

C) minimum sealant.

Leave space so bottom grille can be lowered for trim
door removal.