TZ-3 TOTALZONE® ZONE CONTROL PANEL

68-0223-2

14

Table 6. DIP Switch Settings and Functions.

Table 7. LED Indicators.

DIP Switch

Function

Off (default)

On

1

Staging by number of zones
calling.

Stages timer or thermostat
controlled.

Stages controlled by number of zones
calling.

2

ZMS low limit.

40°F

48°F

3

Purge mode timing.

Three and one-half minutes.

Two minutes.

4

Fan control during purge.

Controlled by panel.

HVAC equipment controlled

5

Control of W2 outpu.t

Timer controlled.

Controlled by W2 from thermostat,

6

Cool changeover from
thermostat.

Not using B on single Y
thermostats; or using
conventional thermostats.

Using B on single Y thermostat.

7

Heat changeover from
thermostat.

Not using O on single Y
thermostats; or using
conventional thermostats.

Using O on single Y thermostat.

8

Fan control in heat.

Fan controlled by panel in cool
and HVAC equipment in heat.

Panel in heat and cool controlling fan.

LED

Color

Illuminated

Not Illuminated

Flashing

Heat

Red

Heat call

No heat calls.

High limit reached

Cool

Green

Cool call

No cool calls.

Low limit reached

Purge

Amber

Purge mode

Not in Purge mode.

ZMS failure

Idle

Red

No calls

Call for heat, cool, or fan.

Initial powerup without ZMS
wired

Fan

Green

Fan only call

No fan only call.

EM Heat

Red

Emergency Heat mode

Not in emergency Heat mode.

Zone 1,2,3

Zone
1,2,3

Green—open
Red—closed
Amber—moving (some
dampers)