TZ-3 TOTALZONE® ZONE CONTROL PANEL

68-0223-2

6

Fig. 9. MARD and CDO-51 Damper wiring.

ML6161 Motor Actuator

When the ML6161 Motor Actuator is used, wire as shown in
Fig. 10. Wire the R8222 relay to prevent the damper LED from
constantly lighting amber.

Fig. 10. ML6161 Damper Motor Actuator wiring.

Transformer

Wire the transformer to the panel as shown in Fig. 11.

NOTE:

If the installation includes an Add-A-Zone panel, see
the TotalZone Add-A-Zone Panels section.

Fig. 11. Transformer wiring.

Discharge Air Temperature Sensor

Wire the C7735A or the ZMS to the panel as shown in Fig. 12.

Fig. 12. Discharge Air Temperature Sensor (C7735A or

ZMS) wiring.

Add-A-Zone Panel

Wire the Add-A-Zone (TAZ) Panel to the TotalZone (TZ-3)
Panel as shown in Fig. 13. Up to nine TAZ Panels can be
wired to one TZ-3 panel. See Fig. 13.

Use 18-gauge thermostat wire for runs up to a maximum of
500 feet. Keep these wires at least 12 in. from line voltage
wiring and equipment; otherwise, use shielded cable wiring.

IMPORTANT:

When multiple panels are used, it is important that
the transformers be in-phase. Check the phasing by
measuring for 24V across the TR2 transformer termi-
nals on each panel. There should be 0 Vac. If not,
reverse the TR1and TR2 transformer wires on one of
the panels and recheck.

Fig. 13. TotalZone Add-A-Zone wiring.

Conventional Equipment

Wire the heating and cooling equipment to the equipment
terminals on the TZ-3 Panel as shown in Fig. 14.

Electric Furnaces: Set DIP switch 8 to On to energize the fan
with a call for heat.

Hydro-Air: Wire the zone valve or circulator relay to the W1
equipment terminal. (If the circulator relay has powered
terminals, use an isolation relay.) Set DIP switch 8 to On to
energize the fan with a call for heat.

Oil Heat: Wire an isolation relay on the W equipment wire to
isolate the oil primary from the panel.

COM / M1

CL / M6

OP / M4

MARD OR CDO-51

ZONE CONTROL PANEL

DAMPER TERMINALS

M19069

M6

M4

M1

COM / M1

CL / M6

OP / M4

ML6161

R8222 RELAY

ZONE CONTROL PANEL

DAMPER TERMINALS

M19070

M6

M4

M1

ZONE

THERMOSTAT

TERMINAL

R

C

24 VOLT
TRANSFORMER

R

TR1

TR2

24V, 40 VA

TRANSFORMER

MODEL AT140D1046

M19071

TL

TL

ZMS

SENSOR

M19072

TO ADDITIONAL

TAZ PANELS

M19073

AZ2

AZ1

TAZ

AZ2

AZ1

TAZ

AZ2

AZ1

TZ-3