Planning the installation – Honeywell F111 Series 1 User Manual

Page 3

Advertising
background image

F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

3

68-0198-2

Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3).

a

Same for Single Speed Models (Series 1 & 2).

.

Fig. 1. Approximate dimensions of F111

(Series 1,2,3) in in. (mm).

Installation Weight:
Approximately 115 lb to 155 lb (kg) depending on the filter

configuration. Refer to Table 3.

Table 3. Sorbent Module Weight.

Sound Level at 3.3 ft (1m):
Low speed: 53 dBA (3 speed models only).
Medium speed: 57 dBA (3 speed models only)
High speed: 61 dBA.

Grille Type: Perforated metal.

Mounting: Recesses into opening on the ceiling.

Approvals:
Underwriters Laboratories Inc.: Listed.
Canadian Standards Association: Listed.

Accessories:
Black Color Grill
Remote 3-Speed Wall Switch

Replacement Parts See Parts List, Table 5.

PLANNING THE INSTALLATION

The number of F111 (series 1,2,3) air cleaners that are needed
is determined by taking into account the number of occupants
and the volume of the space. Type of contamination, outdoor
air quality and use of the area are also factors. Refer to Table
3 for general guidelines when determining how many air
cleaners are needed.

EXAMPLE: One air cleaner can provide 2.5 air changes per

hour in a 24,000 cubic feet (720 cubic meters) no
smoking area. Table 3 suggests two air cleaners
for a 24,000 cubic feet area because most areas
have contaminants that require more units to
provide quality air.

If any questions should arise concerning determining the
number of air cleaners needed for an area, consult your
distributor or local Honeywell Commercial Air Cleaner
Distributor.

Table 4. Determining the Minimum Number of

Air Cleaners Needed for a Space.

Model

Voltage

Particulates at

0.3 Micron

(DOP Test)

Gas, V.O.C. and

Odor Control

Modules (2)

High

a

in cfm

(m

3

/hr)

Medium

in cfm

(m

3

/hr)

Low

in cfm

(m

3

/hr)

F111A1253W-3S 120 Vac, 60 Hz, 8.5A

95% ASHRAE

N/A

1250 (2120)

800 (1360)

450 (760)

F111A1063W-3S 120 Vac, 60 Hz, 7.2A

99.97% HEPA

N/A

950 (1610)

775 (1310)

450 (760)

F111C1073W-3S 120 Vac, 60 Hz, 7.5A

95% ASHRAE

CPZ™ modules 1150 (1950)

825 (1400)

450 (760)

F111C1003W-3S 120 Vac, 60 Hz, 7.0A

99.97% HEPA

CPZ™ modules 825 (1400)

700 (1190)

450 (760)

F111C1012W-3S 120 Vac, 60 Hz, 8.0A

95% at 0.3 micron CPZ™ modules 1125 (1910)

825 (1400)

450 (760)

F111A2253W-3S 230 Vac, 50 Hz, 4.2A

95% ASHRAE

N/A

1125 (1910)

700 (1190)

475 (810)

F111A2007W-3S 230 Vac, 50 Hz, 3.5A

99.97% HEPA

N/A

900 (1530)

600 (1020)

400 (680)

F111C2073W-3S 230 Vac, 50 Hz, 4.0A

95% ASHRAE

CPZ™ modules 1025 (1740)

675 (1150)

450 (760)

F111C2003W-3S 230 Vac, 50 Hz, 3.2A

99.97% HEPA

CPZ™ modules 825 (1400)

550 (930)

375 (640)

F111C1053W-3S 230 Vac, 50 Hz, 3.5A

95% at 0.3 micron CPZ™ modules 950 (1610)

625 (1060)

425 (720)

Media

Weight in lb (kg)

CPZ™ modules (2)

43 (20)

22-1/2 (572)

24 (610)

3/8 X 16
INTERNAL
THREAD (4)

46-3/4 (1187)

48 (1219)

17-1/4

(438)

4-1/2

(114)

TOP VIEW

POWER CONNECTION
POINT

CEILING

LINE

M11996A

Space Volume

(L x W x H) in Cubic

Feet (Cubic Meter)

Number of

Persons Present

Minimum

Number of Air

Cleaners

12000 to 18000

(360 to 540)

30 to 60

1

18001 to 35000

(540 to 1050)

61 to 90

2

Advertising
This manual is related to the following products: