F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

5

68-0198-2

latches (2)

3-speed switch module ( 3 Series only)

Make Opening (if Mounting in a Drop Ceiling)

1.

Size the opening to fit the air cleaner cabinet as closely
as possible.

2.

Frame the opening to provide adequate support for the
cabinet. The cabinet must fit snugly in the opening;
allow no more than 1/4 in. (6 mm) from the opening to
each side of the cabinet.

3.

Cover the framing and any unused portion of the open-
ing with wallboard, plywood, or other material and finish
to match the ceiling.

Electrical Hookup

All wiring must comply with applicable codes and ordinances.
The power source must agree with the model type: 120V,
60 Hz or 230V, 50 Hz.

1.

Locate the prepunched hole in the side of the cabinet.

2.

Remove the air cleaner lid.

3.

For Series 1 and 2 only.Remove the connection box
cover plate in the center cavity of the air cleaner.

4.

For Series 3 only. Remove the connection box cover
plate on the bottom, underneath the tray.

5.

Refer to Fig. 3 and 4 for typical electrical diagrams.

WARNING

Risk of Fire or Electric Shock.
Can cause personal injury or equipment damage.
Use only Honeywell 190097C Remote Speed Switch
(3-speed models only) to regulate air cleaner speed.
Using a different speed switch may void the warranty.

IMPORTANT

Be sure the air cleaner is grounded for correct
operation and safety.

Canadian installation: NEVER install in ceilings with
thermal insulation value greater than R-40.

Fig. 3. Typical F111 (series 1 & 2) 120V, 60 Hz or

208/230V, 50/60 Hz wiring diagram.

Fig. 4. Typical F111 Series 3 only 120V, 60 Hz or

230V, 50 Hz wiring diagram.

Mount Air Cleaner Cabinet

The air cleaner can be mounted in a drop ceiling system or
hung in an open area. Both mounting methods require the air
cleaner to be level and positioned facing downward for correct
operation.

1.

Remove the door/grille from the carton and set it aside.

2.

Remove all filters.

3.

Fit the cabinet into the prepared ceiling opening or
position on the ceiling.

4.

Use the four 3/8 x 16T internal nuts (one at each corner)
to fasten the cabinet to a structural support (bar joist,
concrete slab or timber framing). See Fig. 5.

NOTES:

All external hardware is furnished by the installer.

When using the suspension system of mounting,
be sure to include a means for leveling adjust-
ment after installation.

Never rest the air cleaner on the T-bar.

5.

Level the air cleaner.

6.

Turn the air cleaner power on and check for proper
operation for 2 to 3 minutes. There should be a smooth,
powerful blower sound and air discharging from both
ends of the air cleaner.

7.

Turn off the power.

8.

Install the particle filter. Note airflow direction arrows if
present. Install the filter with the direction arrow pointing
towards the motor.

9.

For Series 1 and 2 only. Fasten the filter tabs. Be sure
there is a snapping sound when fastened. The tabs are
commercial Velcro and require more force than lightly
pushing them together.

10.

For Series 3 only. Lock and secure the particle filter
into place by closing both latches.

M12657

CAPACITOR

WHITE
GREEN

BLACK

FACTORY WIRING

BROWN

EXTERNAL
WIRING BY
INSTALLER

MOTOR

A100002

CAP

ACIT

OR

WHITE
GREEN

BLACK

FACTORY WIRING

BROWN

EXTERNAL

WIRING BY

INSTALLER

MOTOR

BLUE

VIOLET

RED

BLACK

REMOTE 3-SPEED

SWITCH

Advertising