F111 (SERIES 1,2,3) IN CEILING MEDIA AIR CLEANER

68-0198-2 Revised 5-09

6

Fig. 5. Fasten cabinet to a structural support.

IMPORTANT

Do not touch the pleated filter media. Handle only the
filter frame to prevent damage to the filter media.

11.

Remove CPZ™ sorbent modules (select models) from
their packaging and install one module into each cavity.

12.

For Series 1 only. Be sure the fastener tabs are facing
downward and fasten them.

13.

For Series 2 and 3 only. Be sure both catches are
turned down and filter rests firmly on catches.

14.

Install the prefilter in the air cleaner lid. Position the
metal screen mesh so it is facing upward when the lid is
closed.

Remote 3 Speed Wall Switch (3 Speed Models only)

The 190097C Remote Wall Switch Assembly allows control of
the F111 model air cleaners from a a location separate from
the air cleaner. The assembly includes a remote switch with
an outlet box cover, outlet box, extension ring, and a wire
harness. Wiring to connect the remote switch and air cleaner
must be furnished separately.

CAUTION

This installation to be performed only by a qualified
installer.

All wiring to comply with local electrical codes.

Disconnect power to air cleaner at fuse or breaker
before beginning work. Failure to do so can result in
shock hazard endangering equipment and personal
safety of installer.

Only one air cleaner can be connected to a remote
switch

1.

Disconnect power to air cleaner.

2.

Mount 4” x 4” outlet box at desired remote location.

3.

Attach 3/4” extension ring to outlet box.

4.

Run five conductor, color-coded, 18-gauge wires from
the remote switch location to the air cleaner.

5.

Use three wire nuts to connect three color-coded, lead
wires on the remote switch to three color-coded wires
from the air cleaner. (Red, Blue, Violet)

6.

Use one wire nut to connect white color-coded, lead
wire from the air cleaner to single color-coded wire from
the power supply. (White)

Fig. 6. Wiring 3-Speed Remote Switch

7.

Connect the ground wire from the power supply to a
ground stud of the outlet box.(Green)

8.

Connect the ground wire from the air cleaner to the
ground stud of the outlet box.(Green)

9.

Use one wire nut to connect the black color-coded, lead
wire on the remote switch to the black color-coded wire
from the power supply.

10.

Fold wires into box and mount remote switch on outlet
box. Leave switch in OFF position.

11.

On the air cleaner remove two screws on wiring com-
partment cover and open

12.

Run five conductor, color coded, 18 gauge wires from
the remote switch through the air cleaner access open-
ing into the wiring compartment. Strip ends of remote
switch lead wires

13.

Connect three wires on air cleaner to remote switch
lead wires with wire nuts following color code used at
remote switch. (Red, Blue, Violet)

CHAIN

NOTE:
FASTEN SECURELY TO STRUCTURAL
SUPPORT SYSTEM, I.E. BAR JOIST,
CONCRETE SLAB OR TIMBER FRAMING.

HEX BOLT

LOCK
WASHER

M10892

TOP OF METAL CABINET

EYEBOLT

BOTTOM FLANGE AGAINST
UNDERSIDE OF TEES

JAM NUT
3/8 IN. X 16T

"Z" BRACKET (4)

JAM
NUT

THREADED
ROD

BOTTOM VIEW OF
UNIT WITHOUT
LID ASSEMBLY

CEILING
TEE

OR USING OPTIONAL "Z" BRACKETS

TOP OF METAL CABINET

A100001

BLACK