5 interfaces, Interfaces – GE Industrial Solutions Digital Energy SNMP_WEB ADAPTER User Manual

Page 18

Advertising
background image

Connect the power to the box (left-most connector in the picture above). Make sure that the
SNMP/WEB Interface box is powered by the UPS output!

The UPS / Fail LED will switch OFF once the connection to the UPS is established.
If the LED remains continuously on, check the UPS connection and related cabling.




3.5 INTERFACES

UTP 10/100 – RJ45 port
Connection to an Ethernet 10/100 Mbits/s networks, using an UTP cable.

RS-232 – DB9 port
Serial communication, connection to a local console.
Use a straigth (1:1) serial cable for connection to a PC.

1
2
3
4
5
6

1
2
3
4
5
6

2
3

5

4

1

6
7
8
9

TD

RD

2
3

5

4

1

6
7
8
9

TD

RD

Connector pin-out as follows:
Pin #

Function

2

TD – Transmit Data

3

RD – Receive Data

5 GND

Contact interface – RJ11 port (1-ph plug-in version only)
Plug-in contact interface port.

Connector pin-out as follows:
Pin #

Function

1

Mains failure

2

General alarm *

3

Battery low

4

On bypass

5

N.C.

6

GND


(*) Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than
already indicated by pin 1-3-4.

CAUTION !

The DB9 and RJ11 port share the same GND signal.

Exercise caution when both interfaces are used at the
same time, particularly when connecting these interfaces
to non-floating ground systems.


Modifications reserved

Page 18/24

ISG_CNT_SNM_BAS_CRD_1GB_V012.doc

Installation Guide SNMP/Web Adapter