How to set the system clock, Cdt one event timer exerciser – GE ZTGD Series Transfer Switches 40-3000 Amps User Manual

Page 14

Advertising
background image

14

GE Zenith Controls

ZTG/ZTGD Operation and Maintenance Manual (70R-1000D)

How to Set the System Clock

How to Set the System Clock

Set System Clock, time and date

·

If the clock is not set, the display will show
SET SYSTEM CLOCK on the second line
of the S1 OK screen.

·

The S1 OK screen will show time (hours and
minutes) on the second line if the system clock
has been set. (Date on third line)

Setting the System Clock

(Start from S1 OK screen)
1. Remove battery protective white plastic strip

near P relay. *

2. Press MORE then press SET.
3. Press MORE and scroll to SET SYSTEM CLOCK

using the MORE key.

4. Press SEL.
5. ENTER ACCESS CODE located on the white label

on the back of the controller.

6. Press SEL.
7. Use the up and down keys to change the hour value.

8. Press SAVE (this will enter this value and move

cursor to minutes).

9. Use the up and down keys to change the minutes.
10. Press SAVE (this will enter this value and move

cursor to month).

11. Use the up and down key up to change the month.
12. Press SAVE (This will enter this value and complete

the clock setting).

13. Use the up and down keys to change the date.
14. Press SAVE (this will enter this value and move

cursor to year).

15. Use the up and down keys to change year.
16. Press SAVE (this will enter this value and

compete the clock setting).

17. To edit settings, press SEL and repeat steps 6-16.
18. If the setting is satisfactory, press MORE

(unit then returns to the SET menu then
press BACK, then ESC.)

* Replacement battery part #K-4100

Battery will last 5 years and provides power to retain clock
function only (Controller functions without battery).

Load / No-Load

One event Exerciser with adjustable Timer. Exercise
duration can be set between 5 and 60 minutes in
1 minute increments. Can be configured to run every
1,7,14, or 28 days. Factory default is 20 minutes.

How to CONFIGURE (CFG) and Set (SET)
the Timer Exerciser

1. Beginning from the S1 OK screen,

press MORE then CFG.

2. Press MORE to scroll to CONFIG TIMER

EXERCISER

screen.

3. The third line of the CONFG TIMER EXERCISER

will show either DAILY, WEEKLY, 14 DAY, 28 DAY,
or OFF.

4. If the third line of the CONFG TIMER EXERCISER

shows DAILY, WEEKLY, 14 DAY, or 28 DAY as
desired, then proceed to step 10.

5. If the third line of the CONFG TIMER EXERCISER

shows OFF or if another timer selection is desired,
continue.

6. Press SEL.
7. Enter ACCESS code located on white label

on the back of the controller.

8. Press UP or DOWN to select DAILY, WEEKLY,

14 DAY

, or 28 DAY as desired.

9. Press SAVE.
10. Press MORE to scroll to CONFG TIMER

EXERCISER (XFR)

or (NO XFR).

11. Press Up or Down to select XFR (Load Transfer)

or NO XFR (No Load Transfer).

12. Press SAVE.
13. Press MORE repeatedly to BACK then S1 OK screen.

Set (SET) the Exerciser:

14. Beginning from the S1 OK screen,

press MORE then SET.

15. Press MORE repeatedly until

EXER S2 RUN TIME

screen.

16. Press SEL
17. Enter ACCESS code located on white label

on the back of the controller.

18. Press SEL
19. Cursor is indicated as a line under character to

be changed. Change values with up and down keys.

20. Press SAVE when complete.
21. Press MORE repeatedly until SET USER SETUP

then press BACK then ESC to the S1 OK screen.

CDT One Event Timer Exerciser

Advertising