Controls power supply (cps), Standard and delay transition – GE ZTGD Series Transfer Switches 40-3000 Amps User Manual

Page 22

Advertising
background image

22

GE Zenith Controls

ZTG/ZTGD Operation and Maintenance Manual (70R-1000D)

Standard and Delay Transition

Each MX150 microprocessor based ATS controller
requires a Controls Power Supply (CPS) to apply line
voltage to the ATS operator via SCRs. Also required is
power for the MX150 printed circuit board and an
application of sensing voltage proportional to line voltage.

Controls Power Supply (CPS)

This is accomplished by the Controls Power Supply (CPS).
This method of switching operator voltage and applying
power and sensing voltage to the printed circuit board
isolates the MX150 from the line voltage, further protecting
the controller from harmful line transients.

Primary

CPS

CPS

Voltage

Assembly

Board

at 50/60 Hz

Part No.

No.

120V

50P-1224

50P-1200

208-220V

50P-1225

50P-1201

230-240V

50P-1226

50P-1202

277V

50P-1227

50P-1203

380-400V

50P-1228

50P-1204

416-440V

50P-1229

50P-1205

460-480V

50P-1230

50P-1206

575-600V

50P-1231

50P-1207

Advertising