GE 208-277VAC User Manual

Heavy duty mechanical time switch, 24 hour time switch

Advertising
background image

We recommend that installation be made by a licensed electrician.

Disconnect power at main panel prior to installing or servicing this

time switch or the equipment connected to it.

Connect in accordance with national and local electrical codes.

Supply Connections: Use gauge specified (AWG #8-14 ) suitable for 75

º

C

(167

º

F). Replace insulator before turning on electricity to unit.

INSTALLATION AND OPERATING INSTRUCTIONS TO SET ON AND

OFF TIMES:

Light trippers turn ON.

Dark trippers turn OFF. Place tripper on

dial edge as shown in figure and set

point of each tripper to desired oper-

ating time. Note if selected time is AM

or PM. Hold tripper against dial edge

and firmly tighten knurled screw.

208-277VAC/60Hz

O

F

F

O

N

TIM

E

ON TIME

(Light Tripper)

MANUAL

ON

LEVER

MANUAL

OFF

LEVER

OFF TIME

(Dark Tripper)

Knurled Screw

Dial Calibrations

HEAVY DUTY

MECHANICAL

TIME SWITCH

INSTALLATION AND OPERATING INSTRUCTIONS

TO SET DIAL TO TIME:

Turn dial counter-clockwise until correct time is indicated by

arrow on nameplate.

FOR TEMPORARY MANUAL OVERRIDE:

Press down lever on right of nameplate to turn ON. Press down

lever on left of nameplate to turn OFF. CAUTION: Do not rotate

dial for manual override.

TO REMOVE MECHANISM FROM CASE:

Press lever near case latch to release mainplate and swing the

movement out. To replace, insert mainplate projections in slots

opposite latch and swing movement in until it latches.

15307

24 HOUR TIME SWITCH

SWITCH:

DPST

CONTACT RATINGS:

40 AMP 120-277VAC

1000VA (120-277) PILOT DUTY

40 AMP TUNGSTEN 120VAC 120-277VAC SINGLE PHASE

20 AMP INDUCTIVE

2HP 120VAC; 5HP 240VAC

TIMING MOTOR:

208-277VAC 60Hz

POWER CONSUMPTION: 3 WATTS MAX

For seperate motor terminals, remove bridge from terminals L & 1

GE5361-41K2

469D

15307

MANUAL VERSION 1

02/02/10

WWW.JASCOPRODUCTS.COM

L

H

H

N

M

1

X

2

TYPICAL FOR 277V SUPPLY

TYPICAL FOR 277V SUPPLY

Typical for double pole

Cut motor lead at 1

LOAD

LOAD

MUST BE

SAME PHASE

L

H

H

M

1

X

2

LOAD

Advertising