GE Zoneline AZ61H09DAC User Manual

Room air/installation qsart, Az61h09dac, Ge zoneline

Advertising
background image

AZ61H09DAC

GE Zoneline

®

Deluxe Series Heat Pump Unit

Specification Created 12/09

390516

For answers to your Monogram,

®

GE Profile

or

GE

®

appliance questions, visit our website at

ge.com or call GE Answer Center

®

service,

800.626.2000.

Electrical Wiring
All wiring, including installation of receptacle, must be made in accordance with local

electrical codes and regulations.
Note: Aluminum wiring may pose special problems – consult a qualified electrician.
Grille Options
Stamped Aluminum Grille – RAG60
Exterior Architectural Louvers Durable Polycarbonate:
RAG61 (Beige)

RAG63 (Bittersweet)

RAG62 (Maple)

RAG67 (Extruded Aluminum)

Retrofit Kits:
RAK901L – Wall Case Insulation for use with heat pumps.

RAK40 – Deflector Kit to adapt chassis for use with existing

exterior architectural louvered grilles.
Ducted Applications
4100 and 6100 series can be used with ductwork to heat or cool more than one room.

RAK6052 Duct Adaptor is applied to top of case over air discharge/RAK601 Duct

Extension is applied to right or left of adaptor. Locally fabricated ductwork may be

added to extend to maximum recommended distance of 15 feet.
Electrical Connection
230/208 volt units may be plugged into a receptacle. 265 volt units are provided with

a junction box and require direct

connection. (NEC Requires 265V Direct Connection) See Architects and Engineers

Design Data Manual for electrical

connection information including use of sub-base for direct connected units.

Installation must comply with local electrical codes and regulations.
Power Connection kits required on all Zoneline chassis.

Wall Case Dimensions

RAB71 Wall Sleeve

Heavy-gauge galvanized steel, with insulation.

A – 42", B – 13-3/4", C – 16"
RAB77 Wall Sleeve

Molded SMC fiberglass-reinforced polyester compound.

A – 42-1/8", B– 13-7/8", C – 16-1/4

Wall Opening Dimensions

Add 1/4" to A and C dimensions for all cut-out size.

RAB71 16-1/4" Min. H x 42-1/4" Min. W

RAB71 available in 16", 24", 28" and 31" depths

RAB77 16-1/2" Min. H x 42-3/8" Min. W

Maximum Cord Extension

SIDE

VIEW

Inside

Room

Cabinet

Outside

58

21

Grille

7-1/8

RAB71A = 16
RAB77A = 16-1/4

RAB71A = 20-7/8
RAB77A = 21

Room Air/Installation QSart

Dimensions and Installation Information (in inches)

230/208 Volt Line Cord Connected Units

Line Cord

Kit

Electric Heat

(Btuh)

Electric

Heater Watts

Electric

Heat Amps

Min. Circuit

Protection

(Amps)

RAK3153A

8,600/7,100

2,550/2,090

11.6/10.6

15

RAK3203A

11,700/9,600

3,450/2,820

15.5/14.1

20

RAK3303A

17,000/13,900

5,000/4,090

22.3/20.3

30

230/208 Volt Sub-Base Connected Units

Sub-Base

Electric Heat

(Btuh)

Electric

Heater Watts

Electric

Heat Amps

Min. Circuit

Protection

(Amps)

RAK204D15P

8,600/7,100

2,550/2,090

11.6/10.6

15

RAK204D20P 11,700/9,600

3,450/2,820

15.5/14.1

20

RAK204D30P 17,000/13,900

5,000/4,090

22.3/20.3

30

A

C

B

Zoneline RAC Wall Installation

Advertising