Use the correct wall case

This unit is designed to be installed in a GE plastic or
insulated metal wall case. This minimizes condensation
from forming on the room side of the case.

If the current wall case is not insulated, you can reduce
the possibility of condensation forming by installing
insulation kit RAK901L, available where you purchased
the unit.

NOTE: There are several extra holes in the unit side flanges
for installation in wall cases other than GE. To avoid
damaging the flange insulation, the installer should use
an awl or other sharp tool to puncture the insulation in
the appropriate holes before installing the attachment
screws.

Use the correct outdoor grille

You should use the outdoor grilles shown on the
“Essential Elements” label on the base pan.

If an existing grille is not replaced, capacity and

efficiency will be reduced and the unit may fail to
operate properly or fail prematurely. A deflector kit,
RAK40, may be used with grilles that were not designed
for your new GE Zonelines. The RAK40 contains air
deflectors and gaskets that mount to the unit to direct
the hot exhaust air away from the air intake to allow
the unit to function properly. The grille must have a
65% minimum free area.

Any vertical deflectors in the existing rear grille should

be removed to decrease condenser air recirculation
that can cause the unit to “short-cycle” and lead to
premature component failure.

Use the correct power cord

Local codes may require the use of arc fault or leakage
current detection devices on 230/208-volt installations.

Check the “Essential
Elements” label for
important information.

Replacing a ducted unit

New ducted installation:
If this unit is to be installed in a new ducted application
using a duct adapter kit, the kit must be installed before
the unit is placed in the wall case. The installation
instructions are packed with the kit.

Duct kits available:

RAK6052
RAK601/602

Existing ducted installation:
Replacement of an existing ducted unit may require
different components. Request this information from your
sales representative.

• Replacing 230/208 volt units:

See page 13.

• Replacing 265 volt units:

See page 14.

When using a duct kit, you must always turn Mode 7 to
ON "

." See Mode instructions on page 7.