Electrical connection, Electrical connection –16, Power cord connection direct connection – GE Zoneline 4100 User Manual

Page 13

Advertising
background image

Installation Instructions

HOW TO CONNECT

ELECTRICAL SUBBASE
CONNECTION

1. Remove the room cabinet.

2. Connect to electrical power.

3. Review the following steps for applicable supply

voltages.

4. Reinstall the room cabinet.

Tandem

15 Amp.

230/208-volt receptacle configuration.

Perpendicular

20 Amp.

Large Tandem

30 Amp.

Power cords may include an arc fault interruption
or a leakage current detection interruption device.
A test and reset button is provided on the plug case
or the inline case. The device should be tested on
a periodic basis by first pressing the TEST button
and then the RESET button. If the TEST button does
not trip or if the RESET button will not stay engaged,
discontinue use of the Zoneline and contact a
qualified service technician.

230/208-volt models may be installed using one
of the following electrical subbases:

*Not approved for use on 7000 BTU models.

Electrical subbases provide an enclosure for direct
connection or enclosed receptacles. The subbase kit
includes the power cord.

The instructions provided with the selected subbase kit
must be carefully followed. It is the responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes.

Branch Circuit and

Proper GE

Unit Amperage Rating

Subbase Kit

15

RAK204D15P

20

RAK204D20P

30

RAK204D30P*

A power supply kit with LCDI must be used to supply power
to the Zoneline unit. The appropriate kit is determined by
the voltage, the means of electrical connection and
the amperage of the branch circuit.

Connections of 208 or 230-volt circuits may be with a
power supply kit or a junction box kit.

All wiring, including installation of the receptacle, must
be in accordance with the NEC and local codes,
ordinances and regulations. Codes require the use of
an arc fault or leakage current detection device on the
power cord except direct connect. Be sure to select the
correct cord for your installation.

Power supply kit

Appearance may vary.

Branch Circuit and

Proper GE Power Cord

Unit Amperage Rating

with LCDI Device

15

RAK3153

20

RAK3203

30

RAK3303*

230/208 VOLT ELECTRICAL CONNECTION OPTIONS

*Not approved for use on 7000 BTU models.

POWER CORD
CONNECTION

DIRECT CONNECTION

Order the following Kit for 230/208-volt direct
connection as required:

*Not approved for use on 7000 BTU models.

Skip to the “MAKE ELECTRICAL CONNECTION TO THE UNIT”
section.

Branch Circuit and

Power Supply

Power

Unit Amperage Rating

Accessory

Supply Kit

15

RAK4002A

RAK4157

20

RAK4002A

RAK4207

30

RAK4002A

RAK4307*

13