MITSUBISHI ELECTRIC TG-2000A User Manual

Page 44

Advertising
background image

41

8.8.3 Set-up for the Name and the Maximum Integrated Value of WHM (Step 2)

Set the WHM name, location, and maximum integrated value

1) Enter the WHM name and location.

Enter the connected WHM name and location.

2) Set the maximum integrated value.

Use the “ / ” button or numeric input to set the

WHM maximum integrated value.

3) Clic k [ F i n i s h] button.

At the end of setting, click the [ F i n i s h] button.

* If the [Cancel] button is clicked, the settings are

interrupted and the screen returns to the initial
window.











[Reference]

Shows the communication parameters that must be set at the watt hour meter used.












Name and maximum integrated value settings

Note:

• A name and location up to 16 characters long can be entered.
• Always set the WHM maximum integrated value. If the correct maximum integrated value is not

set, the energy monitoring functions will not operate normally.

• When the WHM maximum integrated value is 0, a warning is displayed. Set the WHM maximum

integrated value.

Model

Baud rate

Parity

Stop bit

Notes

P o w e r R a i l 3 2 3

9 6 0 0 b p s

Fixed

Fixed

AEM31D/485

Fixed

Fixed

Fi xed

CVM-BC-ITF-RS485-C2

9 6 0 0 b p s

N o n e

1 b i t

E D 3 9 d i n -4 8 5

9 6 0 0 b p s

N o n e

1 b i t

BCD used as communications protocol.

Items other than the above do not have to be set because they are fixed for each watt hour meter.