Manitowoc Ice K00364 User Manual

Manitowoc Ice Control panel

Advertising
background image


K00364 Electronic Bin Thermostat

Installation Instructions


This kit reduces overfill and condensation issues and can be used on any Manitowoc ice machine installed on an ice
dispenser. Order kit number K00336 for the following models IB0620, IB0820, IB1020, QF0400 and QF2300.

Control Settings

Flake/Nugget/Chiplet:
The control must be reset from the factory setting.
Refer to the jumper and control settings.

Ice Cube Machines:
The machines use the factory control settings.

The controller has a one-minute time delay anytime
power is interrupted and restored.

Positioning the Touchpad Jumpers


P5 Jumper

The P5 jumper position determines if the touchpad is
locked or unlocked. The control is factory locked; to
unlock, move the jumper from one pin to two pins.


P4 Jumper

The P4 jumper labeled Jump 1 is used to set the control
for heating or cooling mode. Jump 2 is used to
establish set point at either cut-in or cut-out.








Cubers

Flake/Nugget/Chiplet


Setting Control Set point Value

To view and adjust set point, follow these steps:

A. Press MENU until the display flashes SP.
B. Press MENU again to display the existing set

point value.

C. Press up or down (arrows) to change the set

point value.

D. Press MENU again to save the new value. The

display returns to the sensed temperature.

E. If no setup entry is made for 30 seconds, the

control reverts to the normal temperature
display.


IMPORTANT:
If MENU is not pressed after changing the set point
value, the control reverts to the previously
programmed set point value.








RED
SENSOR
LEAD

BLACK
SENSOR
LEAD

JUMPER
LOCATIONS

MATCH
WIRING
TO ICE
MACHINE
VOLTAGE

BIN SWITCH OR

TOGGLE SWITCH