Connect the cables in the specified order – Mitsumi electronic Mac E1070 User Manual

Page 10

Advertising
background image

Installation

2-2

Mitsubishi Electric, MA00776

3. Secure the operator terminal in position, using all the fastening holes and the

provided brackets and screws:

4. Connect the cables in the specified order.

Use an M5 screw and a grounding conductor (as short as possible)
with a cross-section of minimum 2.5 mm

2

.

5. Carefully remove the laminated film over the operator terminal display, to avoid

static electricity that could damage the terminal.

x 6

0.5 - 1.0 Nm

B

C

D

A

Caution
Ensure that the operator terminal and the controller system have the
same electrical grounding (reference voltage level), otherwise errors
in communication may occur.

Caution
- Use only shielded communication cables.
- Separate high voltage cables from signal and supply cables.

Caution
- The operator terminal must be brought to ambient temperature

before it is started up. If condensation forms, ensure that the
operator terminal is dry before connecting it to the power outlet.

- Ensure that the voltage and polarity of the power source is correct.

24V DC

RS422/RS485

24V DC

1

CF
CARD

B

A

C

D

RS232

Controller

Power

Ethernet

Advertising
This manual is related to the following products: