1 examples of two-pair wiring (for rs-422 circuit) – MITSUBISHI ELECTRIC FX0N-485ADP User Manual

Page 5

Advertising
background image

*1 R is the terminating resistance. Connect the terminating resistance (330

) between terminals

SDA and SDB , and terminals RDA and RDB . For details see section 2.3.

*2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100

or less. However, as for the computer link unit of the A series PC, see the manual of the computer

link unit.

*3 The 24V DC power requirement can be taker from the service power supply of the PC.

R

*1

(1) When connecting one computer and one PC

Cable connection and signal direction

485PC-IF

Signal name

Application

Reception data

Reception data

Transmission data

Transmission data

Signal ground

Frame ground

Power supply terminal

Power supply terminal

485PC

Signal name

LINK SG

FG

24V

24G

*2

*3

*3

RDA

RDB

SDA

SDB

R

*1

R

1

SDA

SDB

RDA

RDB

R

*1

LINK SG

Computer link unit
of A series PCs

Computer

485ADP

485PC-IF

485ADP

Station

No. 1

Station

No. 15

SDA

SDB

RDA

RDB

SG

FG

SDA

SDB

RDA

RDB

FG

SDA

SDB

RDA

RDB

FG

SDA

SDB

RDA

RDB

SD

RD

SD

RD

R

*1

R

*1

*

2

*

2

*

2

LINK

SG

LINK

SG

LINK

SG

Station

No. 0

(2) Computer and PCs in 1 : n connection ( n has a maximum value of 16 ).

The terminal lagout shown is diagrammatic only. As for 485ADP, see chapter 1, and as for 485PC-IF,
and computer link unit for A series PC, see the individual manuals.

2.1 Examples of two-pair wiring (for RS-422 circuit)

Grounding
resistance of
100

or less

FX base unit

DC24V

R

*1

R

*1

Advertising