2 examples of one-pair wiring (for rs-485 circuit) – MITSUBISHI ELECTRIC FX0N-485ADP User Manual

Page 6

Advertising
background image

*1 R is the terminating resistance. Connect the terminating resistance (110

) between terminals

RDA and RDB . For details see section 2.3.

*2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100

or less. However, as for the computer link unit of the A series PC, see the manual of the computer

link unit.

*3 The 24V DC power requirement can be taker from the service power supply of the PC.

(1) When connecting one computer and one PC

485ADP

485ADP

485ADP

Computer

485PC-IF

Station

No. 1

Station

No. 15

SDA

SDB

RDA

RDB

FG

SDA

SDB

RDA

RDB

FG

SDA

SDB

RDA

RDB

FG

SDA

SDB

RDA

RDB

R

*

1

SD

RD

SD

RD

R

*1

*

2

*

2

*

2

LINK

SG

LINK

SG

LINK

SG

Station

No. 0

LINK

SG

LINK SG

FG

24V

24G

LINK SG

Cable connection and signal direction

485PC-IF

Signal name

Application

Reception data

Reception data

Transmission data

Transmission data

Signal ground

Frame ground

Power supply terminal

Power supply terminal

485ADP

Signal name

RDA

RDB

SDA

SDB

R

*1

SDA

SDB

RDA

RDB

R

*1

*2

*3

*3

2.2 Examples of one-pair wiring (for RS-485 circuit)

Grounding
resistance of
100

or less

FX base unit

DC24V

(2) Computer and PCs in 1 : n connection ( n has a maximum value of 16 ).

The terminal lagout shown is diagrammatic only. As for 485ADP, see chapter 1, and as for 485PC-IF, and
computer link unit for A series PC, see the individual manuals.