Allen-bradley plc 5, slc500 and micrologix plcs, Registers accessed, Protocols supported – ICP DAS USA DB25 User Manual

Page 55: Please note that the micrologix plc only supports, Ge fanuc 90/20, 90/30 and 90/70 plcs

Advertising
background image

Application Notes – PLCs and Devices

49

A

LLEN

-B

RADLEY

PLC

5,

SLC500

AND

M

ICRO

L

OGIX

PLC

S


Registers Accessed
The DN-3000 will only access registers in Integer files in the PLC memory (N file types). When
specifying register numbers in the DN-3000 Configuration Software, the file number is entered into the
File Number field and the element number within the file is entered into the Register Number field.

Protocols Supported
The DN-3000 uses the DF1 protocol, which is also known as Full Duplex or Point to Point. It supports
both the CRC and BCC methods of error checking.

Please note that the MicroLogix PLC only supports the CRC method of error checking. Therefore, when
using a MicroLogix PLC, the protocol selected on the port configuration screen in the DN-3000
Configuration Editor must be “AB SLC500 (CRC)”.


GE

F

ANUC

90/20,

90/30

AND

90/70

PLC

S


Registers Accessed
The DN-3000 will only access registers in the Data Register Area of PLC memory (%R1 to %R9999).
When entering register numbers, only the offset into this area (1-9999) should be entered. For example,
to access register number %R1, the value 1 should be entered. To access register number %R9999, the
value 9999 should be entered.