INSTALLATION INSTRUCTIONS

62-0331-11

JADE

Economizer Module

(MODEL W7220)

This document describes wiring, power up, basic

troubleshooting, and common installation issues for the

JADE™ Economizer Module (Model W7220). For further

information on mounting and operation, refer to Honeywell

document 63-2700.

BEFORE INSTALLATION

Review the following before installing the The W7220:

Electrical

Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz

Transformer: 100 VA maximum system input

Relay Digital Output Rating: 30 Vac

IMPORTANT

All inputs and outputs must be Class 2 wiring.

Inputs

A Mixed air (MA) analog sensor is required on all W7220

units; either an OA (Outdoor Air) sensor for dry bulb change

over or an OA Sylkbus sensor for outdoor enthalpy change

over is required in addition to the MA sensor. An additional

Return Air (RA) Sylkbus sensor can be added to the system

for differential enthalpy changeover.

DCV (CO

2

) Sensor (C7232): 2-10 Vdc control signal;

minimum impedance >50k ohm.

Outputs

Actuator signal: 2-10 Vdc; minimum actuator impedance is

2k ohm; Sylkbus two-wire output for Honeywell Sylkbus

communicating actuators.

Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac)

All Relay Outputs (at 30 Vac):

Running: 1.5A maximum

Inrush: 7.5A maximum

When Installing This Product

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous condi-

tion.

2. Check ratings given in instructions and on the product to

ensure the product is suitable for your application.

3. Installer must be a trained, experienced service techni-

cian.

4. After installation is complete, check out product opera-

tion as provided in these instructions.

5. For additional detailed information on this product go to

customer.honeywell.com and download the product

data sheet (lit no 63-2700) or scan QR code located on

the label above MAT terminals with your smart phone.

Accessories

50048926-001 2-pin edge connector for sensors

(20 pieces per bag)

50048926-002 6-pin edge connector for field wiring

(20 pieces per bag)

C7250 20k sensor for MA or OA (dry bulb changeover)

C7400S Sylkbus sensor for enthalpy control in OA and/or RA

and RA for differential dry bulb changeover

W7220 PCMOD interface tool for JADE controller and Per-

sonal Computer. Go to www.customer.honeywell.com/

economizertools for the software

50053060-001 Duct mounting kit for sensors

C7632 or C7232 CO

2

sensors