John Lewis SCO5JL User Manual

Bedroom, Bedroom hall living room kitchen, Edroom bedroom kitchen lounge dining room

Advertising
background image

General limitations of smoke/CO alarms

Model

SCO5JL

M09-0071-001

Q 05/10

Table of contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Safety Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Basic Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3

Where to Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2

Where This Alarm Should NOT Be Installed . . . . . . . . . . . . . . . . . . .2

How to Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Weekly Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Optional Locking Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3

Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

If Your Smoke/CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

What To Do First–Identify The Type Of Alarm . . . . . . . . . . . . . . . . . .4

If the CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

If the Smoke Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Using the Silence Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

What You Need To Know About CO . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

What is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Symptoms of CO Poisoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Finding the Source of CO After an Alarm . . . . . . . . . . . . . . . . . . . . .5

Potential Sources of CO in the Home . . . . . . . . . . . . . . . . . . . . . . . .5

How Can I Protect My Family From CO Poisoning? . . . . . . . . . . . . . . . . .5

Regulatory Information For Smoke/CO Alarms . . . . . . . . . . . . . . . . . . . .5-6

Regulatory Information for CO Alarms . . . . . . . . . . . . . . . . . . . . . .5-6

Regulatory Information for Smoke Alarms . . . . . . . . . . . . . . . . . . . . .6

Recommended Locations for Smoke Alarms . . . . . . . . . . . . . . . . . . .6

About Smoke Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Special Compliance Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7

Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7

General Limitations of Smoke/CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . .7

Limited Guarantee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
John Lewis Partnership

171 Victoria Street

London SW1E 5NN

www.johnlewis.com

Introduction

Important safety information

It is most important this instruction book be retained with the appliance

for future reference.These warning have been provided in the interest of

safety.You MUST read them carefully before using the appliance. If you are

unsure of the meanings of these warnings contact the John Lewis branch

from which you purchased the appliance.

Safety tips

Follow safety rules and prevent hazardous situations: 1) Use smoking

materials properly. Never smoke in bed. 2) Keep matches or lighters away

from children; 3) Store flammable materials in proper containers; 4) Keep

electrical appliances in good condition and don’t overload mains circuits;

5) Keep cookers, barbecue grills, fireplaces and chimneys grease- and

debris-free; 6) Never leave anything heating on the cooker unattended;

7) Keep portable heaters and open flames, like candles, away from flamma-

ble materials; 8) Don’t let rubbish accumulate.
Keep alarms clean, and test them weekly. Replace alarms immediately if

they are not working properly. Smoke Alarms that do not work cannot

alert you to a fire. Keep at least one working fire extinguisher on every

floor, and an additional one in the kitchen along with a fire blanket. Have

fire escape ladders or other reliable means of escape from an upper floor

in case stairs are blocked.

Basic safety information

• Dangers,Warnings, and Cautions alert you to important operating

instructions or to potentially hazardous situations. Pay special

attention to these items.

• This Smoke/CO Alarm is approved for use in single-family

residences. It is NOT designed for boat or caravan use.

• This combination Smoke/Carbon Monoxide Alarm has two separate

alarms.The CO Alarm is not designed to detect fire or any other gas.

It will only indicate the presence of carbon monoxide gas at the sen-

sor. Carbon monoxide gas may be present in other areas.The Smoke

Alarm will only indicate the presence of smoke that reaches the sen-

sor.The Smoke Alarm is not designed to sense gas, heat or flames.

• This Smoke/CO Alarm cannot operate without working batteries.

Removing the batteries for any reason, or failing to replace the

batteries at the end of their service life, removes your protection.

• NEVER ignore any alarm. See “If Your Smoke/CO Alarm Sounds”

for more information on how to respond to an alarm. Failure to

respond can result in injury or death.

• The Silence Feature is for your convenience only and will not correct a

Smoke/CO problem.Always check your home for a potential problem

after any alarm. Failure to do so can result in injury or death.

• Test this Smoke/CO Alarm once a week. If the Alarm ever fails

to test correctly, have it replaced immediately! If the Alarm is not

working properly, it cannot alert you to a problem.

• This product is intended for use in ordinary indoor locations of family

living units. It is not designed to measure CO levels in compliance with

Occupational Safety and Health Administration (OSHA) commercial or

industrial standards. Individuals with medical conditions that may make

them more sensitive to carbon monoxide may consider using warning

devices which provide audible and visual signals for carbon monoxide

concentrations under 30 ppm. For additional information on carbon

monoxide and your medical condition contact your GP.

• Do not install the Alarm where it may be exposed to dripping water

or could be splashed.

5

6

7

2

3

Combination carbon

monoxide and smoke alarm

4

M09-0071-001 Q 05/10

What you need to know about CO

What is CO?

CO is an invisible, odorless, tasteless gas produced when fossil fuels do not

burn completely, or are exposed to heat (usually fire). Electrical appliances

typically do not produce CO.
These fuels include:Wood, coal, charcoal, oil, natural gas, gasoline,

kerosene, and propane.
Common appliances are often sources of CO. If they are not properly

maintained, are improperly ventilated, or malfunction, CO levels can rise

quickly. CO is a real danger now that homes are more energy efficient.

“Air-tight” homes with added insulation, sealed windows, and other

weatherproofing can “trap” CO inside.

Symptoms of CO poisoning

The following symptoms are related to CARBON MONOXIDE POISONING

and are to be discussed with ALL members of the household:

Fuel-burning appliances like: portable heater, gas or wood burning fireplace,

gas kitchen range or cooktop, gas clothes dryer.
Damaged or insufficient venting: corroded or disconnected water heater

vent pipe, leaking chimney pipe or flue, or cracked heat exchanger, blocked

or clogged chimney opening.
Improper use of appliance/device: operating a barbecue grill or vehicle in

an enclosed area (like a garage or screened porch).
Transient CO Problems:“transient” or on-again-off-again CO problems

can be caused by outdoor conditions and other special circumstances.
The following conditions can result in transient CO situations:
1. Excessive spillage or reverse venting of fuel appliances caused by

outdoor conditions such as:
• Wind direction and/or velocity, including high, gusty winds.

Heavy air in the vent pipes (cold/humid air with extended periods

between cycles).

• Negative pressure differential resulting from the use of exhaust fans.
• Several appliances running at the same time competing for limited

fresh air.

• Vent pipe connections vibrating loose from clothes dryers, boilers,

or water heaters.

• Obstructions in or unconventional vent pipe designs which can

amplify the above situations.

2. Extended operation of unvented fuel burning devices (range, oven,

fireplace).

3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home

.

These conditions are dangerous because they can trap exhaust in your

home. Since these conditions can come and go, they are also hard to

recreate during a CO investigation.

How can I protect my family from CO poisoning?

A CO Alarm is an excellent means of protection. It monitors the air and

sounds a loud alarm before Carbon Monoxide levels become threatening

for average, healthy adults.
A CO Alarm is not a substitute for proper maintenance of home appliances.
To help prevent CO problems and reduce the risk of CO poisoning:

• Clean chimneys and flues yearly. Keep them free of debris, leaves,

and nests for proper air flow.Also, have a professional check for

rust and corrosion, cracks, or separations.These conditions can

prevent proper air movement and cause backdrafting. Never “cap”

or cover a chimney in any way that would block air flow.

• Test and maintain all fuel-burning equipment annually. In the case

of gas appliances, this must be a CORGI registered installer. Many

local gas or oil companies and heating companies offer appliance

maintenance and inspection contracts.When service technicians/

engineers come to service your heating and cooking appliances,

ensure the following checks are carried out if you are unable to do

them yourself.

• Make regular visual inspections of all fuel-burning appliances. Check

appliances for excessive rust and scaling.Also check the flame on

the burner and pilot lights.The flame should be blue.A yellow flame

means fuel is not being burned completely and CO may be present.

Keep the blower door on the boiler closed. Use vents or fans when

they are available on all fuel-burning appliances. Make sure appli-

ances are vented to the outside. Do not grill or barbecue indoors,

or in garages or on screen porches.

• Check for exhaust backflow from CO sources. Check the draft

hood on an operating boiler for a backdraft. Look for cracks on

boiler heat exchangers.

• Check the house or garage on the other side of shared wall.
• Keep windows and doors open slightly. If you suspect that CO is

escaping into your home, open a window or a door. Opening win-

dows and doors can significantly decrease CO levels.

In addition, familiarize yourself with all enclosed materials. Read this manual

in its entirety, and make sure you understand what to do if your CO Alarm

sounds.

Regulatory information for smoke/CO alarms

Regulatory information for CO alarms

What levels of CO cause an alarm?

Underwriters Laboratories Inc. Standard UL2034 requires residential CO

Alarms to sound when exposed to levels of CO and exposure times as

described below.They are measured in parts per million (ppm) of CO over

time (in minutes).
UL2034 Required Alarm Points*:

• If the alarm is exposed to 400 ppm of CO, IT MUST ALARM

BETWEEN 4 and 15 MINUTES.

• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM

BETWEEN 10 and 50 MINUTES.

• If the alarm is exposed to 70 ppm if CO, IT MUST ALARM

BETWEEN 60 and 240 MINUTES.

* Approximately 10% COHb exposure at levels of 10% to 95% Relative

Humidity (RH).
The unit is designed not to alarm when exposed to a constant level of 30

ppm for 30 days.

CO Alarms are designed to alarm before there is an immediate life threat.

Since you cannot see or smell CO, never assume it’s not present.
• An exposure to 100 ppm of CO for 20 minutes may not affect average,

healthy adults, but after 4 hours the same level may cause headaches.

• An exposure to 400 ppm of CO may cause headaches in average,

healthy adults after 35 minutes, but can cause death after 2 hours.

This CO Alarm measures exposure to CO over time. It alarms if CO

levels are extremely high in a short period of time, or if CO levels reach

a certain minimum over a long period of time.The CO Alarm generally

sounds an alarm before the onset of symptoms in average, healthy adults.

Continued...

Regulatory information for CO alarms, continued
Why is this important? Because you need to be warned of a potential CO

problem while you can still react in time. In many reported cases of CO

exposure, victims may be aware that they are not feeling well, but become

disoriented and can no longer react well enough to exit the building or

get help.Also, young children and pets may be the first affected.

The average healthy adult might not feel any symptoms when the CO

Alarm sounds. However, people with cardiac or respiratory problems,

infants, unborn babies, pregnant mothers, or elderly people can be more

quickly and severely affected by CO. If you experience even mild symptoms

of CO poisoning, consult a doctor immediately!
Standards: Underwriters Laboratories Inc. Single and Multiple Station

arbon monoxide alarms UL2034.
According to Underwriters Laboratories Inc. UL2034, Section 1-1.2:

“Carbon monoxide alarms covered by these requirements are intended to

respond to the presence of carbon monoxide from sources such as, but

not limited to, exhaust from internal-combustion engines, abnormal opera-

tion of fuel-fired appliances, and fireplaces. CO Alarms are intended to

alarm at carbon monoxide levels below those that could cause a loss of

ability to react to the dangers of Carbon Monoxide exposure.” This CO

Alarm monitors the air at the Alarm, and is designed to alarm before CO

levels become life threatening.This allows you precious time to leave the

house and correct the problem.This is only possible if Alarms are located,

installed, and maintained as described in this manual.
Gas Detection at Typical Temperature and Humidity Ranges:The CO

Alarm is not formulated to detect CO levels below 30 ppm typically. UL

tested for false alarm resistance to Methane (500 ppm), Butane (300 ppm),

Heptane (500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol (200 ppm)

and Carbon Dioxide (5000 ppm).Values measure gas and vapor concen-

trations in parts per million.
Audible Alarm: 85 dB minimum at 3 metres (10 feet).

LIMITED GUARANTEE

John Lewis Plc., (“the Company”), guarantees its enclosed Smoke/Carbon Monoxide

Alarm – but not the battery – to be free from defects in materials and

workmanship under normal use and service for a period of five years from the

date of purchase.
John Lewis Plc. makes no other express guarantee for this unit.

No agent, representative, dealer or employee of the Company has the authority

to increase or alter the obligations or limitations of the Guarantee.
The Company’s obligation of this Guarantee shall be limited to the repair or

replacement of any part of the alarm which is found to be defective in materials

or workmanship under normal use and service during the guarantee period

commencing with date of purchase.The Company shall not be obligated to repair

or replace alarms which are found to be in need of repair because of damage,

unreasonable use, modifications or alterations occurring after the date of purchase.
How to Obtain Guarantee Service

Service: If replacement is required, return the product to your retailer.

Battery: John Lewis Plc. make no guarantee, express or implied, written or oral,

including that of merchantability or fitness for any particular purpose with respect

to battery.

The smoke alarm component of this product conforms to regulatory

requirements, including UL217 and is designed to detect particles of

combustion. Smoke particles of varying number and size are produced in

all fires.

Ionization technology is generally more sensitive than photoelectric

technology at detecting small particles, which tend to be produced

in greater amounts by flaming fires, which consume combustible

materials rapidly and spread quickly. Sources of these fires may include

paper burning in a wastebasket, or a grease fire in the kitchen.

Photoelectric technology is generally more sensitive than ionization

technology at detecting large particles, which tend to be produced

in greater amounts by smoldering fires, which may smolder for

hours before bursting into flame. Sources of these fires may include

cigarettes burning in couches or bedding.

For your records, please record:

Date Purchased __________ Where Purchased ___________________

This Smoke/CO Alarm is intended for residential use. It is not intended

for use in industrial applications where Occupational Safety and Health

Administration (OSHA) requirements for Carbon Monoxide Alarms must

be met.The Smoke Alarm portion of this device is not intended to alert

hearing impaired residents. Special purpose Smoke Alarms should be

installed for hearing impaired residents (CO Alarms are not yet available

for the hearing impaired).
Smoke/CO Alarms may not waken all individuals. Practice the escape plan

at least twice a year, making sure that everyone is involved – from kids to

grandparents.Allow children to master fire escape planning and practice

before holding a fire drill at night when they are sleeping. If children or

others do not readily waken to the sound of the Smoke/CO Alarm, or if

there are infants or family members with mobility limitations, make sure

that someone is assigned to assist them in fire drill and in the event of

an emergency. It is recommended that you hold a fire drill while family

members are sleeping in order to determine their response to the sound

of the Smoke/CO Alarm while sleeping and to determine whether they

may need assistance in the event of an emergency.
Smoke/CO Alarms cannot work without power. Battery operated units

cannot work if the batteries are missing, disconnected or dead, if the wrong

type of batteries are used, or if the batteries are not installed correctly.

AC units cannot work if the AC power is cut off for any reason (open fuse

or circuit breaker, failure along an electrical main or at a power station,

electrical fire that burns the electrical wires, etc.). If you are concerned

about the limitations of battery or AC power, install both types of units.
Smoke/CO Alarms cannot sense smoke or CO that does not reach the

sensors. Smoke or CO from fires in chimneys or walls, on roofs, or on the

other side of closed doors may not reach the sensing chamber and set off

the alarm.That is why one unit should be installed inside each bedroom or

sleeping area—especially if bedroom or sleeping area doors are closed at

night—and in the hallway between them.
Smoke/CO Alarms may not detect smoke or CO on another floor or area

of the home. For example, a stand-alone unit on the second floor may not

detect smoke from a ground floor fire until the fire spreads.This may not

give you enough time to escape safely.That is why recommended minimum

protection is at least one unit in all circulation spaces (normally hallways

and staircases) that form part of escape routes, on every level, and in all

rooms and areas that present a high risk. Even with a unit on every floor,

stand-alone units may not provide as much protection as interconnected

units, especially if the fire starts in a remote area. Some safety experts rec-

ommend installing interconnected mains (AC) powered units with battery

(DC) back-up (see “About Smoke Alarms”) or professional fire detection

systems, so if one unit senses smoke or CO, all units alarm. Interconnected

units may provide earlier warning than stand-alone units since all units

alarm when one detects smoke or CO.
Smoke/CO Alarms may not be heard.Though the alarm horn in this unit

meets or exceeds current Standards, it may not be heard if: 1) the unit is

located outside a closed or partially closed door, 2) residents recently

consumed alcohol or drugs, 3) the alarm is drowned out by noise from

stereo,TV, traffic, air conditioner or other appliances, 4) residents are hear-

ing impaired or sound sleepers. Special purpose units, like those with visual

and audible alarms, etc. should be installed for hearing impaired residents.

Smoke/CO Alarms are not foolproof. Like any electronic device, Smoke/CO

Alarms are made of components that can wear out or fail at any time.

You must test the unit weekly to ensure your continued protection.

Smoke/CO Alarms cannot prevent or extinguish fires.They are not a

substitute for property or life insurance.
Smoke/CO Alarms have a limited life.The unit should be replaced

immediately if it is not operating properly. Smoke alarms are not to be

used with detector guards unless the combination has been evaluated and

found suitable for that purpose. Write the purchase date on the user’s

manual and keep in a safe place for future reference.

Instruction manual

HOW TO INSTALL THIS ALARM

This combination Smoke/CO Alarm was designed to be mounted on the

ceiling or wall. It is not a tabletop device.You must install this device on

the ceiling or wall as outlined below. Read “Where To Install This Alarm”

before starting.

Tools you will need: pencil, drill with 5mm (3/16”) drill bit,

flathead screwdriver, hammer.

• Do not connect this unit to any other alarm or auxiliary device. It is a

single-station unit that cannot be linked to other devices. Connecting

anything else to this unit may prevent it from working properly.

• Do not install this unit over mains cables or holes into the ceiling.

Air currents will prevent smoke from reaching the sensing chamber

and prevent the unit from alarming. Only AC powered units are

intended for installation over mains cables.

If you want to lock the battery compartment, or lock the Smoke/CO

Alarm to the mounting bracket, please read the “Optional Locking

Features” section.
1. Hold base firmly and twist the mounting bracket counterclockwise

(left) to separate it from the unit.

2. Hold the mounting bracket against the ceiling (or wall) so the vertical

mounting slot is aligned in the 12 o’clock position and trace around

the inside of the mounting slots (vertical and horizontal mounting).

3. Put the unit where it won’t get covered with dust when you drill the

mounting holes.

4. Using a 5 mm (3/16-inch) drill bit, drill a hole through each pencil mark.
5. Insert the plastic screw anchors into the holes.Tap the screw anchors

gently with a hammer, if necessary, until they are flush with the ceiling

or wall.

6. Line the mounting bracket up over the plastic screw anchors.
7. Screw the mounting bracket to the ceiling or wall through the mount-

ing slots using the two screws provided.

8. Before attaching the Alarm to

the bracket, insert the two (2)

AA batteries (included) into the

battery compartment. Match

the terminals on the end of the

battery with the terminals on

the unit. Match “+” to “+” and

“-” to “-.” If the batteries are not

fully inserted, the unit cannot

receive battery power.

NOTE:The unit may beep briefly when you install the batteries.This is

normal.The GREEN Light flashes about every 60 seconds when the

unit is receiving battery power.

The battery door will resist closing unless batteries are installed.This

warns you the unit will not operate without batteries.
9. Attach the Smoke/CO Alarm to the

mounting bracket. Line up the guides on

the alarm’s base with the guides on the

mounting bracket.When guides are

lined up, turn the base clockwise (right)

until it snaps into place.
NOTE: Once the Smoke/CO Alarm is

snapped onto the mounting bracket,

you can rotate the Smoke/CO Alarm

to adjust the alignment.

10. Test the Smoke/CO Alarm. See “Weekly

Testing” for details.

If the CO alarm sounds

Actuation of your CO Alarm indicates the presence of carbon monoxide

(CO) which can kill you. In other words, when your CO Alarm sounds,

you must not ignore it!
If the CO alarm signal sounds:

1. Operate the Test/Silence button.
2. Call your emergency services or Fire Brigade (like 999 in the UK or

112 in Europe).Write down the number of your local emergency

service here:
_________________________________________________________

3. Immediately move to fresh air—outdoors or by an open door or win-

dow. Do a head count to check that all persons are accounted for. Do

not re-enter the premises, or move away from the open door or win-

dow until the emergency services responder has arrived, the premises

have been aired out, and your CO Alarm remains in its normal condition.

4. After following steps 1-3, if your CO Alarm reactivates within a 24-hour

period, repeat steps 1-3 and call a qualified appliance technician to

investigate for sources of CO from fuel-burning equipment and appli-

ances, and inspect for proper operation of this equipment. If problems

are identified during this inspection have the equipment serviced

immediately. Note any combustion equipment not inspected by the

technician, and consult the manufacturers’ instructions, or contact the

manufacturers directly, for more information about CO safety and this

equipment. Make sure that motor vehicles are not, and have not, been

operating in an attached garage or adjacent to the residence.Write

down the number of a qualified appliance technician here:
_________________________________________________________

“ALARM-MOVE TO FRESH AIR”

If you hear the alarm horn sound 4 beeps, pause, 4 beeps, pause and the

RED CO light is flashing, move everyone to a source of fresh air.

If the smoke alarm sounds

Responding to an alarm

• If the unit alarms and you are not testing the unit, it is warning you

of a potentially dangerous situation that requires your immediate

attention. NEVER ignore any alarm. Ignoring the alarm may result in

injury or death.

• Never remove the batteries from a battery operated Smoke/CO

Alarm to stop an unwanted alarm (caused by cooking smoke, etc.).

Removing batteries disables the alarm so it cannot sense smoke,

and removes your protection. Instead open a window or fan the

smoke away from the unit.The alarm will reset automatically.

• If the unit alarms get everyone out of the house immediately.
What to do in case of fire

• Don’t panic; stay calm. Follow your family escape plan.
• Get out of the house as quickly as possible. Don’t stop to get

dressed or collect anything.

• Feel doors with the back of your hand before opening them.

If a door is cool, open it slowly. Don’t open a hot door. Keep doors

and windows closed, unless you must escape through them.

• Cover your nose and mouth with a cloth (preferably damp).

Take short, shallow breaths.

• Meet at your planned meeting place outside your home,

and do a head count to make sure everybody got out safely.

• Call the Fire Brigade as soon as possible from outside.

Give your address, then your name.

• Never go back inside a burning building for any reason.
• Contact your Fire Brigade for ideas on making your home safer.

Alarms have various limitations. See "General Limitations of Smoke/CO

Alarms" for details.

Using the silence feature

Never remove the batteries to quiet an unwanted alarm. Removing the

batteries disables the alarm and removes your protection.
The Silence Feature is intended to temporarily silence the horn while you

identify and correct the problem. Do not use the Silence Feature in emer-

gency situations. It will not correct a CO problem or extinguish a fire.
To use the Silence Feature, press and hold the Test/Silence button on the

cover of the Smoke/CO Alarm for 3 seconds.

Regular maintenance

This unit has been designed to be as maintenance-free as possible, but

there are a few simple things you must do to keep it working properly.

Use only the replacement batteries listed below.The unit may not operate

properly with other batteries. Never use rechargeable batteries since they

may not provide a constant charge.
• Test it at least once a week.
• Clean the Smoke/CO Alarm at least once a month; gently vacuum the

outside of the Smoke/CO Alarm using your household vacuum’s soft

brush attachment.A can of clean compressed air (sold at computer or

office supply stores) may also be used. Follow manufacturer instructions

for use.Test the Smoke/CO Alarm. Never use water, cleaners or

solvents since they may damage the unit.

• If the Smoke/CO Alarm becomes contaminated by excessive dirt, dust

and/or grime, and cannot be cleaned to avoid unwanted alarms, replace

the unit immediately.

• Relocate the unit if it sounds frequent unwanted alarms. See “Where

This Alarm Should Not Be Installed” for details.

Choosing a replacement battery:
Your smoke/CO Alarm requires two AA Energizer E91 batteries. These

Actual battery service life depends on the Smoke/CO Alarm and the

environment in which it is installed.All the batteries specified above are

acceptable replacement batteries for this unit. Regardless of the manufactur-

er’s suggested battery life, you MUST replace the battery immediately once

the unit starts “chirping” (the “low battery warning”).

PARTS OF THIS SMOKE/CO ALARM
1 Test/Silence Button
2 Battery Compartment
3 Power/Smoke Alarm LED
4 CO Alarm LED

To replace the batteries (without removing

Alarm from the ceiling or wall):
1. Open the battery compartment.
2. Press tabs A and B as shown in the diagram

and remove each battery.

3. Insert the new batteries, making sure

they snap completely into the battery

compartment. Match the terminals on

the ends of the batteries with the terminals

on the unit.

4. Close the battery compartment, and then

test the unit by pressing the Test/Silence

button.

AB

Regulatory information for smoke alarms

British standards (BSI) recommendations
BS 5839 part 6 (Code of practice for the design and installation of fire

detection and alarm systems in dwellings)
Smoke Alarms shall be installed in all circulation spaces (normally hallways

and staircases) that form part of escape routes, one on every level, and in

all rooms and areas that present a high fire risk.Additionally, Smoke Alarms

should also be installed between the sleeping area(s) and the most likely

sources of fire (living room and kitchen).
If there are long hallways, corridors, or protected rooms or areas over 7.5

metres (25 feet) from the nearest unit, the installation of additional Smoke

Alarms may be necessary. Roof voids containing stored combustibles or

sources of ignition may also warrant the installation of additional Smoke Alarms.
The installation of Smoke Alarms in kitchens, toilets, bathrooms or shower

rooms is not recommended, as these locations occasionally experience

conditions that can result in improper operation.
More specifically, install smoke alarms:

• Where temperatures normally remain between 4.4˚C (40˚F) and

• On every level of your home, including finished lofts.

• Inside every bedroom, especially if people sleep with doors closed.

• In the hall near every sleeping area. If your home has multiple sleeping

areas, install a unit in each. If a hall is over 7.5 metres (25 feet) long,

install an alarm at each end.

• At the top of the first-to-second floor and subsequent floor stairways,

and at the bottom of the ground floor stairway.

Specific requirements for Smoke Alarm installation may vary from region to

region. Check with your local Fire Brigade and Building Control for current

requirements in your area.

About smoke alarms

Battery (DC) powered smoke alarms: Provide protection even when

electricity fails, provided the batteries are fresh and correctly installed. Units

are easy to install, and do not require professional installation. May also be

interconnected, model dependent, so if one unit senses smoke, all units alarm.
Mains (AC) powered smoke alarms: Can be interconnected so if one unit

senses smoke, all units alarm.They do not operate if electricity fails. Mains (AC)

with battery (DC) back-up: will operate if electricity fails,

are fresh and correctly installed. Mains (AC) powered and mains powered with

battery back-up (AC/DC) units must be installed by a qualified electrician.
All these Smoke Alarms are designed to provide early warning of fires if

located, installed and cared for as described in the user’s manual, and if smoke

reaches them. If you are unsure which type of Smoke Alarm to install, refer to

British Standard (BS) 5839 Part 6 and 5588 Part 1. BSI, 389 Chiswick High

Road, London,W4 4AL, UK. Local building regulations may also require

specific units in new construction or in different areas of the home.

Special compliance considerations

This Smoke Alarm alone is not a suitable substitute for complete fire detection

systems in places housing many people—like blocks of flats (communal escape

routes), hotels, motels, hostels, inns, hospitals, long-term health care facilities,

nursing homes, day care facilities, boarding houses or sheltered housing of any

kind—even if they were once single-family residences.

Continued...

Special compliance considerations, continued
It is not a suitable substitute for complete fire detection systems in ware-

houses, industrial facilities, commercial buildings, and special-purpose non-

residential buildings which require special fire detection and alarm systems.

Depending on the building regulations in your area, this Smoke Alarm may

be used to provide additional protection in these facilities.
The following information applies to all four building types below:
In new construction, most building regulations require the use of mains

(AC) or mains powered with integral standby supply (AC/DC) Smoke

Alarms only. In existing construction, mains powered (AC), mains powered

with integral standby supply (AC/DC), or battery (DC) powered Smoke

Alarms can be used as specified by local building regulations. Refer to

British Standard BS 5839 Part 6 and BS 5588 Part 1, local buildings regula-

tions, or consult your Fire Brigade for detailed fire protection requirements

in buildings not defined as “dwellings.”
1. Single-family residence: Single family home. It is recommended Smoke

Alarms be installed in all circulation spaces (normally hallways and staircases)

that form part of escape routes, on every level, in all rooms and areas that

present a high fire risk and between the sleeping area(s) and the most likely

sources of fire (living room and kitchen).
2. Multi-family or mixed occupant residence: Blocks of flats.This Smoke

Alarm is suitable for use in individual flats, provided a primary fire detec-

tion system already exists to meet fire detection requirements in common

areas like foyers, hallways, corridors, or porches. Using this Smoke Alarm in

common areas may not provide sufficient warning to all residents or meet

local fire protection by-laws/regulations.
3. Institutions: Hospitals, day care facilities, long-term health care facilities.

This Smoke Alarm may be suitable for use in individual patient sleeping/

resident rooms, provided a primary fire detection system already exists to

meet fire detection requirements in common areas like foyers, hallways,

corridors, or porches. Using this Smoke Alarm in common areas may not

provide sufficient warning to all residents or meet local fire protection

by-laws/regulations.
4. Hotels and motels:Also hostels, inns, boarding houses and sheltered

housing.This Smoke Alarm may be suitable for use inside individual sleeping/

resident rooms, provided a primary fire detection system already exists to

meet fire detection requirements in common areas like foyers, hallways,

corridors, or porches. Using this Smoke Alarm in common areas may not

provide sufficient warning to all residents or meet local fire protection

by-laws/regulations.

• When installing on the wall, the top edge of Smoke/CO Alarms should

be placed between 102 mm (4 inches) and 305 mm (12 inches) from

the wall/ceiling line.

• When installing on the ceiling, place the alarm as close to the center as

possible.

• In either case, install at least 102 mm (4 inches) from where the wall

and ceiling meet. See “Avoiding Dead Air Spaces” for more information.

NOTE: For any location, make sure no door or other obstruction could

keep carbon monoxide or smoke from reaching the Alarm.

Where this alarm should NOT be installed

Do NOT locate this Smoke/CO Alarm:

• In garages, kitchens, boiler rooms, crawl spaces and unfinished lofts.

Avoid extremely dusty, dirty or greasy areas.

• Where combustion particles are produced. Combustion particles form

when something burns.Areas to avoid include poorly ventilated

kitchens, garages, and boiler rooms. Keep units at least 6 metres (20

feet) from the sources of combustion particles (cooker, boiler, water

heater, space heater) if possible. In areas where a 6-metre (20-foot)

distance is not possible – in modular, mobile, or smaller homes, for

example – it is recommended the Smoke/CO Alarm be placed as far

from these fuel-burning sources as possible.The placement recommen-

dations are intended to keep these Alarms at a reasonable distance

from a fuel-burning source, and thus reduce “unwanted” alarms.

Unwanted alarms can occur if a Smoke/CO Alarm is placed directly

next to a fuel-burning source.Ventilate these areas as much as possible.

• Within 1.5 metres (5 feet) of any cooking appliance. In air streams near

kitchens.Air currents can draw cooking smoke into the smoke sensor

and cause unwanted alarms.

• In extremely humid areas.This Alarm should be at least 3 metres (10

feet) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry

room, utility room, or other source of high humidity.

• In direct sunlight.
• In turbulent air, like near ceiling fans or open windows. Blowing air may

prevent CO or smoke from reaching the sensors.

• In areas where temperature is colder than 4.4˚C (40˚F) or hotter than

37.8˚C (100˚F).These areas include non-airconditioned crawl spaces,

unfinished lofts, uninsulated or poorly insulated ceilings, porches, and

garages.

• In insect infested areas. Insects can clog the openings to the sensing

chamber.

• Less than 305 mm (12 inches) away from fluorescent lights. Electrical

“noise” can interfere with the sensor.

• In “dead air” spaces. See “Avoiding Dead Air Spaces”.

Avoiding dead air spaces
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm.

To avoid dead air spaces, follow installation recommendations below.
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as

possible. If this is not possible, install the Smoke/CO Alarm at least 102 mm

(4 inches) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/

CO Alarms should be placed between 150 mm (6 inches) and 305 mm

(12 inches) from the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm

within 0.9 metres (3 feet) of the peak of the ceiling, measured horizontally.

Additional Smoke/CO Alarms may be required depending on the length,

angle, etc. of the ceiling's slope. Refer to BS 5839 Part 6, 5588 Part 1 and

local building regulations for details on requirements for sloped or peaked

ceilings.

Where to install this alarm, continued

More specifically, install combination Smoke/CO Alarms:
• Where temperatures normally remain between 4.4˚C (40˚F) and

37.8˚C (100˚F).

• On every level of your home, including finished lofts.
• Inside every bedroom, especially if people sleep with doors closed.
• In the hall near every sleeping area. If your home has multiple sleeping

areas, install a unit in each. If a hall is over 7.5 metres (25 feet) long,

install an alarm at each end.

• At the top of the first-to-second floor and subsequent floor stairways,

and at the bottom of the ground floor stairway.

This equipment should be installed in accordance with the National Fire

Protection Association’s Standard 72 (Batterymarch Park, Quincy, MA 02269).

Specific requirements for Smoke/CO Alarm installation may vary from region

to region. Check with your local Fire Brigade and Building Control for

current requirements in your area.

INSTALLATION

Where to install this alarm

Installing Smoke Alarms in Single-Family Residences
British Standards (BSI) recommend as a minimum one Smoke Alarm on

every floor of your home, and between sleeping areas and potential

sources of fire such as living rooms and kitchens. In single storey homes

with one sleeping area a Smoke Alarm should be installed in the hallway, as

close as possible to the living accommodation. See “British Standards (BSI)

Recommendations” for details. For additional coverage, it is recommended

that you also install a Smoke Alarm in bedrooms in anticipation of fires

originating there, in halls, storage areas, finished loft and roof voids. Make

sure no door or other obstruction could keep smoke from reaching the

Smoke Alarms or minimize the sound level produced from ensuring the

occupants from hearing the alarm signal.

Bedroom

Bedroom

Kitchen

Living rm

Garage

Combination carbon monoxide and smoke alarms
For added protection

If you hear the alarm horn sound 3 beeps, pause, 3 beeps, pause and

the RED SMOKE light is flashing, smoke has been detected.

Evacuate everyone from the building.

When the smoke alarm is silenced

When the CO alarm is silenced

The Smoke Alarm will remain

silent for 15 minutes, then return

to normal operation.
If the smoke has not cleared–or

continues to increase – the device

will go back into alarm.

The CO alarm will remain silent

for 4 minutes.
After 4 minutes, if CO levels

remain potentially dangerous the

horn will start sounding again.

Type of alarm
Carbon Monoxide (CO)

What you see and hear
CO LED: Flashing RED

Horn: 4 beeps, pause, 4 beeps, pause

Power/Smoke LED: Off

D

E

R

g

n

i

h

s

a

l

F

:

D

E

L

e

k

o

m

S

/

r

e

w

o

P

e

k

o

m

S

Horn: 3 beeps, pause, 3 beeps, pause

CO LED: Off

If your smoke/CO alarm sounds
What to do first—identify the type of alarm

TO LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you

activate the battery and test the Smoke/CO Alarm.
1. Install the batteries before attaching the Alarm

to the bracket. Insert the two (2) AA batteries

(included) into the battery compartment.

Match the terminals on the end of the battery

with the terminals on the unit. Match “+” to

“+” and “-” to “-.” If the batteries are not fully

inserted, the unit cannot receive battery

power.

2. Push and hold Test/Silence button until the

alarm sounds.

If the unit does not alarm during testing, DO NOT

lock the battery compartment! Install new batter-

ies and test again. If the unit still does not alarm,

replace it immediately.
3. Using needle-nose pliers or a utility knife,

detach one locking pin from the mounting

bracket.

4. Push the locking pin through the hole near

the battery door latch on the back of the

Smoke/CO Alarm.

OPTIONAL LOCKING FEATURES

TO LOCK THE MOUNTING BRACKET

1. Using needle-nose pliers or a utility knife,

detach one locking pin from the mounting

bracket.

2. Insert the locking pin through the hole

on the back of the Smoke/CO Alarm as

shown in the diagram.

3. When you attach the Smoke/CO Alarm to

the mounting bracket, the locking pin’s

head will fit into a notch on the bracket.

The optional locking features are designed to discourage unauthorized removal of the batteries or Alarm. It is not necessary to activate the locks in

single-family households where unauthorized battery or Alarm removal is not a concern.
This Smoke/CO Alarm has two separate locking features: one to lock the battery compartment, and the other to lock the

Smoke/CO Alarm to the mounting bracket.You can choose to use either feature independently, or use them both.

Tools you will need: • Needle-nose pliers or utility knife • Standard flathead screwdriver.

Both locking features use locking pins, which are moulded into the mounting bracket. Depending on which locking features

you use, remove one or both pins from the mounting bracket using needle-nose pliers or a utility knife.To permanently

remove either locking pin, insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.

TO UNLOCK THE BATTERY COMPARTMENT
1. Remove the Smoke/CO Alarm from the

mounting bracket. If the unit is locked to

the bracket, see the section “To Unlock

the Mounting Bracket.”

2. Insert a flathead screwdriver under the

head of the locking pin, and gently pry it

out of the battery compartment lock.

(If you plan to relock the battery compart-

ment, save the locking pin.)

3. To relock the battery compartment, close

the battery door and reinsert locking pin in

lock.

4. Reattach the Smoke/CO Alarm to the

mounting bracket.

When replacing the batteries, always test the

Smoke/CO Alarm before re-locking the battery

compartment.

TO UNLOCK THE MOUNTING BRACKET

1. Insert a flathead screwdriver into the

rectangular cut-out on the mounting

bracket nearest to the locking pin.

2. Pry the Smoke/CO Alarm away from the

bracket by pushing up on the screwdriver

and turning the Smoke/CO Alarm counter-

clockwise (left) at the same time.

WEEKLY TESTING

This symbol indicates that this product should not be treated

as normal household waste and it should be recycled. John Lewis do not

operate instore takeback, but as members of the Distributor Take Back

scheme have funded the development and upgrade of recycling facilities

across the UK. Please take it to your nearest collection facility or for

further details contact your local council or visit www.recycle-more.co.uk.

1

Recommended locations for smoke alarms

BEDROOM

BEDROOM

HALL

LIVING ROOM

KITCHEN

RECOMMENDATIONS

PROTECTION

EDROOM

BEDROOM

KITCHEN

LOUNGE

DINING ROOM

MULTI-STORY RESIDENCE

MOBILE HOME

KEY:

E

X

IS

T

IN

G

H

O

M

E

S

B

A

T

T

E

R

Y

P

O

W

E

R

E

D

Bedroom

Bedroom

Hall

Bedroom

Kitchen

Kitchen

Living rm

Multi-storey residence

Required to

meet BSI

recommendations

Recommended

for additional

protection

Key:

Single-storey residence, flat, mobile home

Living rm

Dining rm

Bedroom

Bedroom

Kitchen

Bedroom

Garage

Living rm

• NEVER use an open flame of any kind to test this unit.You might

accidentally damage or set fire to the unit or to your home.

The built-in test switch accurately tests the unit’s operation.

• DO NOT stand close to the Alarm when the horn is sounding.

Exposure at close range may be harmful to your hearing.

When testing, step away when horn starts sounding.

It is important to test this unit every week to make sure it is working

properly. Using the test button is the recommended way to test this

Smoke/CO Alarm.
Push and hold the Test/Silence button 3-5 seconds until unit starts to alarm.

• The Alarm horn will sound 3 beeps, pause, 3 beeps.The

Power/Smoke LED flashes Red and the CO LED will be Off.

• Next the horn will sound 4 beeps, pause, 4 beeps.The Power/Smoke

LED will be Off and the CO LED flashes Red.

If the unit does not alarm, make sure the batteries are correctly installed,

and test again. If the unit still does not alarm, replace it immediately.

1. Mild Exposure: Slight headache, nausea, vomiting, fatigue (often described

as "Flu-like" symptoms).

2. Medium Exposure: Severe throbbing headache, drowsiness, confusion,

fast heart rate.

3. Extreme Exposure: Unconsciousness, convulsions, cardiorespiratory

failure, death.

4. Many cases of reported CARBON MONOXIDE POISONING indicate that

while victims are aware they are not well, they become so disoriented they

are unable to save themselves by either exiting the building or calling for

assistance. Young children and household pets are typically the first affected.

The Alarm may not have time to alarm before the fire itself causes damage,

injury, or death, since smoke from some fires may not reach the unit

immediately. Examples of this include children playing with matches, fires

caused by violent explosions resulting from escaping gas or fires where the

victim is in contact with burning materials such as a mattress.

Replace alarm 60 months
after installation.

Recommended Placement

Some individuals are more sensitive to CO than others, including people

with cardiac or respiratory problems, infants, unborn babies, pregnant

mothers, or elderly people can be more quickly and severely affected by

CO. Members of sensitive populations should consult their doctors for

advice on taking additional precautions.

Finding the source of CO after an alarm

Carbon monoxide is an odorless, invisible gas, which often makes it difficult

to locate the source of CO after an alarm.These are a few of the factors

that can make it difficult to locate sources of CO:

• House well ventilated before the investigator arrives.
• Problem caused by “backdrafting.”
• Transient CO problem caused by special circumstances.

Because CO may dissipate by the time an investigator arrives, it may be

difficult to locate the source of CO. John Lewis shall not be obligated to

pay for any carbon monoxide investigation or service call.

Potential sources of
CO in the home

provided the batteries

Troubleshooting guide

If the alarm...

Pr

..

.

d

l

u

o

h

s

u

o

Y

..

.

m

e

l

b

o

Horn "chirps" about once per min

.

s

e

i

r

e

t

t

a

b

A

A

w

e

n

o

w

t

l

l

a

t

s

n

I

.

g

n

i

n

r

a

w

y

r

e

t

t

a

b

w

o

L

.

e

t

u

Horn does three rapid "chirps" every minute;

LED has 3 rapid flashes with "chirps".

Device is not working properly, and needs to be

replaced.

Units under guarantee should be returned to

manufacturer for replacement. See “Limited

Guarantee” for details.

Carbon Monoxide alarm ONLY:
CO Alarm goes back into alarm 4 minutes after

you press the Test/Silence button.

CO levels indicate a potentially dangerous situation.

IF YOU ARE FEELING SYMPTOMS OF CO

POISONING, EVACUATE your home and call 999

or the Fire Brigade. If not, press the Test/Silence

button again and keep ventilating your home.

CO Alarm sounds frequently even though no high

levels of CO are revealed in an investigation.

The CO Alarm may be improperly located. Refer

to “Where to Install This Alarm” for details.

Relocate your Alarm. If frequent alarms continue,

have home rechecked for potential CO problems.

You may be experiencing an intermittent CO

problem.

Smoke alarm ONLY:
Smoke Alarm sounds when no smoke is visible.

Unwanted alarm may be caused by

non-emergency source like cooking smoke.

Clean the Alarm’s cover with a soft, clean cloth.

If frequent unwanted alarms continue, relocate

your Alarm.Alarm may be too close to a kitchen,

cooking appliance, or steamy bathroom.

END OF LIFE SIGNAL.

Alarm needs to be replaced.

The light flashes (RED) and the horn sounds

5 "chirps" every minute.

Immediately replace the Alarm.

For any technical queries or clarification please call the customer helpline on 01452 887570

For your information, the National Fire Alarm Code, NFPA 72, reads as follows:

11.5.1 *Required Detection.
1. *In all sleeping rooms and guest rooms.

2. *Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of

any door to a sleeping room, the distance measured along a path of travel.

3. On every level of a dwelling unit, including basements.

4. On every level of a residential board and care occupancy (small facility),

including basements and excluding crawl spaces and unfinished attics.

5. *In the living area(s) of a guest suite.

6. In the living area(s) of a residential board and care occupancy.

37.8˚C (100˚F).

are commonly available at local retail stores.