Sharp JW-21MN User Manual

Page 100

Advertising
background image

16-5

- When the master station indicates error code 6F

(H)

and the COMM lamp lights.

The cause may be a setting error of any of the slave stations which are set in the parameter.

Check the following master station parameters.

When slave station is JW-21MN, see "Chapter 11: Setting of Switches and Parameter" for

setting range.

- When the master station is normal and the error code 6F

(H)

of a slave station lights.

The cause may be a faulty setting of the slave station parameter. Check the following slave

station parameters.

When slave station is JW-21MN, see "Chapter 11: Setting of Switches and Parameter" for

setting range.

(3) During initial communication (startup of the system)

Lighting error code 6F

(H)

- When the master station indicates error code 6F

(H)

and the COMM lamp is OFF.

The cause may be a parameter setting error of the master station. Check the master station

parameters below.

Amount of connectable
stations

Reference page of the
setting contents

Parameter address

(8)

Setting item

11-5 to 9

005000 to 050001

005200 to 005201

004000 to 004001

004002

004400 to 004403

007764 to 007767

Register link top address
of master station

Relay link transmit
bytes of master station

Register link transmit
bytes of master station

Relay link top address
of master station

Flag top address

Parameter address

(8)

Setting item

004004 to 004377

Reference page of the
setting contents

Relay link top address of
each slave station.
Number of offset bytes.

Register link top address
of each slave station.
Number of offset bytes.

Relay link transmit bytes
of each slave station

Register link transmit
bytes of each slave station

004404 to 004777

005002 to 005177

005202 to 005377

11-5 to 9

Setting item

Parameter address

(8)

Reference page of the

Flag top address

007764 to 007767

11- 22

Advertising