11-4 Setting slave station parameters (common for all slave stations)

When the JW-21MN is used as a slave station, set the following items for parameters.

[1] Setting contents

E0

01

00

80

e

1

to

e

n

i

1

to

i

n

Setting item

V2

Number of receiving bytes of
relay link in save memory
function

Set the number of bytes by decimals. (0 to 256)
- If 0 is set, the number of bytes will be the same
as the number of the sending bytes which is set
in the master station

007720
007721

00

V2

Number of receiving bytes of
register link in save memory
function

Set the number of bytes by decimals. (0 to 2048)
- If 0 is set, the number of bytes will be the same
as the number of the sending bytes which is set
in the master station

007722
007723

00

00

V2

Whether the station number
information should be output
or not

Top address of flag area
(communication and PC
operation condition monitor
flag)

- Start/stop operation of the
JW-21MN
- Writing to EEPROM of the
JW-21MN

Store the number of own statin in the data memory

when setting on 01

(H)

. (storage area of 1 byte follows

flag area of 24 bytes, valid when 007767

(8)

is 80

(H)

)

Lower of file address

Upper of file address

File number

Flag output (Yes: 80

(H)

No: 00

(H)

)

00

(H)

: Stop operation

01

(H)

: Start operation

80

(H)

: Writing to the EEPROM, stop operation

81

(H)

: Writing to the EEPROM, start operation

08

(H)

: Parameter initializing

007763

007777

01

007764

007765

007766

007767

Initial value: 01E0

(H)

000740

(8)

( 0740)

h

1

to

h

n

Address

(8

)

Contents

Initial

value

(H)

Corresponding

signs on pages

11-7 to 11-9

*2

*1

*1: Set only when the memory capacity save function is used.
*2: "Whether the station number information should be output or not" is a unique function of the

JW-21MN.

- Parameter addresses other than above mentioned are reserved areas and prohibited to be

changed.

- When any slave stations are except JW-21MN, see the instruction manual of each device.