1. Low or no voltage.
2. Fuse(s) blown.
3. Customer interlock not closed

or connected.

4. Fan Off-On switch in Off position.
5. Time clock, night setback thermo-

stat or field installed controls
open.

6. Freeze protection tripped.

7. Damper motor not operating, or

its end switch not making.

8. Overload protection on motor

starter tripped.

9. Belts loose or broken

10. Bearings seized.
11. Motor may be burned or incor-

rectly wired.

12. Motor overheating.

1. Heat Off-On switch in Off

position.

2. Burner enable relay open

(if applicable).

3. Outside air temperature higher

than On-Off inlet ductstat
(if applicable).

4. Field purge timer open

(if applicable).

1. Manual gas shut-off valve closed.
2. Inlet gas pressure lower than

required gas pressure.

3. Type of gas (Natural, LP) supplied

different from factory required
type.

4. Auxiliary switch on starter not

closed.

5. Air flow switches not closing.

6. High temperature limit switch

open.

7. High or low gas pressure switches

open (if applicable).

8. Main gas valve relay open.

8

SECTION VII – TROUBLESHOOTING

Symptom

Cause

Remedy

A.

If blower does not operate.

B.

If there is no voltage at ignition
control.

C. Burner does not light after 5 sec-

onds pre purge of flame safeguard
relay and there is voltage at igni-
tion control.

1. Check power source.
2. Check and replace.
3. Close or connect customer

interlock.

4. Switch to On position.
5. Check time clock, night setback

thermostat and field installed
controls for proper settings.

6. Reset freeze stat by interrupting

power. Check for proper setting
and burner operation.

7. Check for power at damper motor

and that end switch has been wired
correctly to the N.O. (normally
open) contact. Check that the
linkage is clear and not binding.

8. Push reset button on starter and

check amps.

9. Turn power off and check belts.

10. Check and replace.
11. Turn power off and check motor

and wiring.

12. Check burner firing rate.

1. Switch to On position.

2. Check for power and replace if

necessary.

3. Lower On-Off inlet ductstat

setting.

4. Check for power and replace if

necessary.

1. Slowly open valve.
2. Increase gas pressure.

3. Replace with factory required

type of gas.

4. Check for power and replace if

necessary.

5. Adjust the air flow and external

static pressure to match rating
plate.

6. Correct problem. Reset by pushing

down the reset button.

7. Correct problem. Reset both

switches.

8. Check for power and replace if

necessary.

System without Pilot