2 connecting the 24 v dc power supply – Siemens Simatic Industrial PC IPC427C User Manual

Page 34

Advertising
background image

Connecting

6.2 Connecting the 24 V DC power supply

SIMATIC IPC427C

34

Operating Instructions, 04/2009, A5E02414743-01

6.2

Connecting the 24 V DC power supply

To be noted before you connect the device

Note the following in order to operate the device safely and according to regulation:

WARNING

The device should only be connected to a 24V DC power supply which satisfies the

requirements of safe extra low voltage (SELV).
If the device is used on a wall, in an open rack or other similar locations, an NEC Class 2

current source is required in order to meet the UL requirements (UL 60950-1). In all other

cases (IEC / EN / DIN EN 609501) either a current source of limited output (LPS = Low

Power Source), or a line-side fuse or a line-side circuit breaker is necessary. The power

needs to be limited to a value below 4.16 A. The fuse value required: Max. 4 A.
Use the special plug supplied to connect the supply voltage. Connect the PE conductors as

described in the next section.

NOTICE

The permitted cable cross-section for the 24 VDC connection is 0.75 mm

2

to 2.5 mm

2

.

NOTICE

If a CompactFlash card is used in the device, make sure that the card is seated correctly

before you connect it.

Connecting

Steps for connecting the device to the 24 V DC power supply
1. Switch off the 24 V DC power source.
2. Connect the power supply using the plug

(included in the package).

3. Connect the PE conductor.