Simpson Electric 501 User Manual

501 insulation tester, Ordering information, Specifications

Advertising
background image

Five Test Voltages: 50, 100, 250, 500, and 1000 VDC

Voltage Measurement to 1000 V AC/DC

Test Probe Signal Lamp Illuminates Work Area and Indicates Pass/Fail of
Insulation Resistance

Battery Powered with Battery Test and Battery Charge Indicator

Rugged Tester Design for Industrial Applications with Leatherette Carrying Case

501 Insulation Tester

The model 501 can be used for general purpose insulation tests that require voltages

from 50V to 1000V only.
The Instrument is equipped with AC and DC measuring ranges up to 1000V. This is
advantageous for testing for the absence of voltage and the discharge of capacitive
devices under test.
The 501 features a quick testing signal lamp within the test probe that illuminates the
work area. The signal lamp can also be used for quick Pass/Fail evaluations of
insulation resistances. Minimum values for insulation resistances are present if the
lamp lights up.
Comes equipped with built-in test probes, an alligator clip, a leatherette carrying case
and batteries.

Ordering Information

ACCESSORIES

Catalog No.

501 Insulation Tester, 1000 V

12501

INSULATION RESISTANCE

DIRECT AND ALTERNATING CURRENT

(1) Referring to scale length

REFERENCE CONDITIONS
Ambient Temperature:
73

ЊF (23ЊC) Ϯ 4ЊF (2ЊC)

Relative Humidity: 45 to 55%
Measurement Magnitude Frequency: 45-65 Hz (voltage measurements)
Line Voltage Waveform: Sine, deviation between effective and rectified value < .5%
Battery Voltage: 9V

Ϯ .5V

Operating Position: Horizontal

ELECTROMAGNETIC COMPATIBILITY EMC
Interference Emission:
EN 50081-1: 1992
Interference Immunity:
EN 50082-1: 1992

ELECTRICAL SAFETY
Designed to IEC 1010-1
Protection Class:
II
Test Voltage:

Ϸ 5.55Kv

Overvoltage Classification: II
Pollution Degree: 2
Protection: Housing IP52

AMBIENT CONDITIONS
Operating Temp. Range:
32

ЊF (0ЊC) to 104ЊF (40ЊC)

Storage Temp. Range: -4

ЊF (-20ЊC) to 140ЊF (60ЊC) (without batteries)

Relative Humidity: Max. 45-55%, condensation must be avoided
MECHANICAL DESIGN
Dimensions:

W 6.50” (165mm) x

D 4.33” (110mm) x H 4.92” (125mm)
Weight: 3.5 lbs. (1.6kg) (with batteries)

POWER SUPPLY
Standard or Storage Battery:
6 ea. 1.5V “D” size batteries
Working Range: 7V to 10V
Battery Service Life: Number of possible measurements with 1 set of “D” size
batteries (with lamp in test prod switched off): at least 3,000 measurements of an
insulation resistance of 1M

⍀ (Nominal Voltage of1000 V, 5 sec. Measurement duration,

switched off for 25 sec. etc.)

Specifications

(1) Switching Accuracy

Measuring Ranges

Measuring

Range

Open-Circuit Voltage

U

o

Internal Resistance R

i

Lamp in Test Prod

1)

Lights for Resistance

0…50K

20K

⍀…1M⍀

200K

⍀…20M⍀

60V

30K

10K

40K

> 100K

0…100K

40K

⍀…2M⍀

400K

⍀…40M⍀

120V

60K

20K

80K

> 200K

0…250K

100K

⍀…5M⍀

1M

⍀…100M⍀

300V

150K

50K

200K

> 500K

0…500K

200K

⍀…10M⍀

2M

⍀…200M⍀

600V

300K

100K

400K

> 1M

0…1M

400K

⍀…20M⍀

4M

⍀…400K⍀

1200V

600K

200K

800K

> 2M

0…4K

9V

Ϫ

Ϫ

Measuring

Range

Frequency

Internal

Resistance

Maximam

Overload

Intrinsic Error (1)

0 to 1000V

AC/DC

0 or 40 to 200Hz

900K

1200V AC/DC

Continuous

Ϯ2.5%

rev_1 11/2/04