System Sensor FTX-P1 User Manual

Ftx-p1 filtrex, Intelligent photoelectronic smoke detector

Advertising
background image

D200-72-00

1

I56-1184-04R

FTX-P1 Filtrex

®

Intelligent

Photoelectronic Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing
This detector must be installed in compliance with the
control panel system installation manual. The installation
must meet the requirements of the Authority Having Juris-
diction (AHJ). Detectors offer maximum performance
when installed in compliance with the National Fire Pro-
tection Association (NFPA); see NFPA 72.

General Description

Filtrex® uses a small air intake fan and a high density re-
placeable filter. Air and smoke are drawn into a photoelec-
tric sensing chamber while airborne particulate and water
mist are removed. The addressable-analog detector trans-
mits an analog representation of smoke density over a com-
munication line to a control panel. Rotary-decade switches
are provided for setting the sensor’s address. Two LEDs on
the sensor are controlled by the panel to indicate sensor
status.

Filtrex smoke detector is intended for use in normal en-
vironmental conditions, where dust and other airborne
particulate are present at elevated levels. These elevated
levels tend to cause false alarms and high maintenance
in standard detectors. Filtrex provides a protective enclo-
sure for a photoelectric smoke detector chamber and al-
lows smoke detection in areas that tended to use
exclusively heat detection.

Filtrex requires compatible addressable communications
to function properly. Connect this detector to listed-com-
patible control panels only.

Spacing
System Sensor recommends spacing detectors in compli-
ance with NFPA 72. In low air flow applications with
smooth ceilings, space detectors 30 feet apart. For specific
information regarding sensor spacing, placement, and spe-
cial applications, refer to NFPA 72 or the System Sensor
Guide For Proper Use of System Smoke Detectors, available
from System Sensor (P/N I56-407-XX).

WARNING

Filtrex is not designed to operate in explosive environments.

Specifications
Operating Voltage Range:

15 to 32 VDC

Detector Current:

230

µ

A @ 24 VDC (without communication)

285

µ

A @ 24 VDC (one communication every 5 sec. with LED enabled)

Auxiliary Power Supply Voltage:

15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.

Auxilary Power Supply Current –

Peak:

123 mA max.

Average:

27 mA max.

Operating Humidity Range:

10% to 93% Relative Humidity, noncondensing

Operating Temperature Range:

0

°

to 50

°

C (32

°

to 122

°

F)

Height:

2.8 inches (43 mm)

Diameter:

6.1 inches (155 mm) installed in B501B-FTX
4.0 inches (102 mm) installed in B524FTXE

Weight:

7.3 oz. (207 g)

Compatibility:

Backwards compatible with 200 and 500 series products’ protocol

Mounting Base:

Requires B501B-FTX (U.S.), B524FTXE (Europe)

Advertising