Connection configuration #1, Solid copper wire – Sundance Spas Spas 880 Series User Manual

Page 25

Advertising
background image

23

A pressure sensitive
terminal block (bonding
lug) is attached to the
outside surface of the
load box. This permits the
connection of a bonding
wire between this point
and any metal equipment
chassis, metal water pipe,
or metal conduit within 5
ft (1.5m) of the spa. The
bonding wire must be at
least #8 AWG (8.4 mm

²

)

solid copper wire.

Red (L2)

Red (L2)

Pigtail

Neutral Bus

Ground

TB2

Black (L1)

Black (L1)

Green

GFCI Sub Panel*

Main Panel*

2-Pole

GFCI

Breaker

Ground/Bonding Lug**

No Load Neutral Wire

Main Panel with Secondary GFCI Shut-Off Box Using a

2-Pole GFCI Breaker with 2-Wire Grounded Connection

(3 Wires to Hot Tub, 2-Hot (L1-L2), 1-Ground)

TB1

White (N)
Green (Ground)

*GFCI Sub Panel commonly

used when recommended GFCI

does not install in Main Panel.

Note: service disconnect not

shown in this diagram.

The control box TB1 terminal

position varies between models.

B

R

Hot Tub

Contr

ol Box

Red (L2)

Pigtail

Neutral Bus

Ground

TB2

TB1

Black (L1)

Green

Main

Service

Panel

with

GFCI

2-Pole

GFCI

Breaker

Ground/Bonding Lug**

2-Pole Circuit Breaker with 2-Wire Grounded Load Connection

(3 Wires to Hot Tub, 2-Hot (L1-L2), 1-Ground)

White (N)

Black (L1)

Red (L2)

240 VAC

No Load Neutral Wire

Note: service disconnect not

shown in this diagram.

The control box TB1 terminal

position varies between models.

B

R

Hot Tub

Contr

ol Box

Connection Configuration #1
240 vAC Connections for 880 Altamar, Cameo, Capri, Majesta, Marin,
Optima, Maxxus, 780 Camden, Certa, Chelsee, Hamilton Models, 680
Burlington, Hartford, Hawthorne Models (North America 60 Hz)