Sharp JW-20CM User Manual

Page 127

Advertising
background image

9

·

29

File address: OCT (octal), word

File number/flag: HEX (hexadecimal), byte

From the previous page

Set top address of relay link area.

· Set file address in parameter address 007730 to 007733

(8)

.

These top addresses should not overlap the register link area, flag area, or any area used by

other option module.

In case of setting 1000 (file address 001000

(8)

) using JW-13PG : Example for slave station 02 of

page 9·41.

“When PC is JW model and the memory capacity save function is used”

Set register link area of register link area.

· Set file address in parameter address 007734 to 007737

(8)

.

These top addresses should not overlap the relay link area, flag area, or any area used by other

option module.

In case of setting 09000 (file address 004000

(8)

) using JW-13PG : Example for slave station 02 of

page 9·41.

To the next page

Screen display of JW-13PG

Screen display of JW-13PG

Lower

Upper

00

(H)

007730

(8)

007731

(8)

007732

(8)

007733

(8)

File address

7

7

MNTR

1

Write 001000

(8)

Write parameter address 007732 to 007733

(8)

for 000000

(8)

.

Display the contents of parameter address
007730 to 007731

(8)

.

07726 0 000000
07730 0 001000

I PARAM.
>07732 0 000000

Lower

Upper

File number

File address

007734

(8)

007735

(8)

007736

(8)

007737

(8)

4

Write parameter address 007734 to
007735

(8)

for 004000

(8)

.

Write parameter address 007736

(8)

for file number 0.

07716 D 00000
07720 D 00004

I PARAM.
>07722 D 00008

V5

V5

File address: OCT (octal), word

File number/flag: HEX (hexadecimal), byte

“When PC is JW model and the memory capacity save function is used”

Advertising