3 cable wiring procedure in control panel – Sharp JW-20CM User Manual

Page 31

Advertising
background image

7

·

2

[1] Fixing of the cable

In order not to put any force on the cable and the

JW-20CM, fasten the cable to an line nearby input

of a control panel or a “T” branch point to the JW-

20CM using saddles etc.

[2] Extra length of cable

Provide an extra length of the cable of 2 to 3 m

inside a control panel for easier processing of the

cable end and easier wiring when changing module

positions.

[3] Connection to the JW-20CM

The connector to the JW-20CM should be turned

right to secure locking, not merely inserted.

[4] Insulation cover

When the connector touches with a high voltage

section or external enclosures, communication

errors may occur. Make sure to install an insulation

cover.

7-3 Cable wiring procedure in control panel

Saddle

Saddle

JW-20CM

Communication cable

connection connector

“L” jacket

(insulation cover)

“T” jacket

(insulation cover)