8.4. Con nec tion of Re turn Air Cooler (Op tional)

F

A re turn air cooler must be em ployed if the re turn air tem per a ture is
higher than +65 °C (149°F).

You can con nect the re turn air cooler to a cool ant cir cuit or to the wa ter mains net work.

The wa ter flow rate in the wa ter mains net work

*

is for:

STT 110. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approx. 0.35 m3/h (12.46 cf/h)
STT 160 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . approx. 0.48 m3/h (17.05 cf/h)
(

*

wa ter tem per a ture: +6 °C) (42.8°F)

Rate your cool ant cir cuit ac cord ingly.

Con nect the cool ant in- and out lets to the re turn air cooler.

Ob serve the flow ing di rec tion of the cool ant.

Check the tight ness of the con nec tions.

5

0

6-

2

M

S

STT 110 / STT 160

As sem bly in struc tions 8-4

STT 110 / STT 160

Con nec ti on of the re turn air coo ler