Generator ac lead connections, Alternator power winding connections, Four-lead, single-phase stator – LG 30kW User Manual

Page 12: Phase alternators, Standby generator sets general information

Advertising
background image

GENERATOR AC LEAD CONNECTIONS

See “Voltage Codes”. This generator may be rated
at any one of three voltages, either single-phase or
three-phase. The electrical wires in the unit’s AC con-
nection (lower) panel should be installed according to
the number of leads and the voltage/phase required
for the application. If there are any questions regard-
ing lead connection, refer to the wiring diagrams at
the back of this manual.

Voltage codes apply to the type of stator assembly
installed on a particular generator.

FOUR-LEAD, SINGLE-PHASE STATOR

Four-lead generators (see Figure 7.1) are designed to
supply electrical loads with voltage code “A” (240V,
1-phase, 60 Hz). Electrical power is produced in the
stator power windings. These windings were con-
nected at the factory to the main circuit breaker as
shown in Figure 7.1.

The rated voltage between each circuit breaker ter-
minal is 240V. The rated voltage between each circuit
breaker terminal and the neutral point 00 is 120V.

Figure 7.1 — Four-lead, Single-phase Stator

‹

ALTERNATOR POWER WINDING
CONNECTIONS

3-PHASE ALTERNATORS

The generator is designed to supply 3-phase electri-
cal loads. Electric power is produced in the alterna-
tor power windings. These windings were connected
at the factory to the main circuit breaker with a “Y”
configuration as shown in Figures 7.2 and 7.3.

The rated voltage between circuit breaker terminals
E1-E2, E1-E3 and E2-E3 is either 480V or 208V
depending on the model.

The rated voltage between each circuit breaker termi-
nal and the neutral point 00 is either 277V or 120V
depending on the model.

Figure 7.2 — Stator Power Winding

Connections - 3-phase, 277/480V (6 Lead)

S6

E3 S3

INTERNAL

CONNECTIONS

L-N

L-L

S4

E2

S2

S5

S1 E1

NEUTRAL

Figure 7.3 — Stator Power Winding

Connections - 3-phase, 120/208V (6 Lead)

E3

E2

00 (NEUTRAL)

E1

L-L

L-N

S1

S1

S4

S4

S6

S6

S3

S3

S5

S5

S2

S2

‹

7-1

Standby Generator Sets

General Information

ACConn001 Re

v. 0 08/05

Advertising
This manual is related to the following products: