Chapter 11. Monitoring

12: During run



Become active when run command is given and the inverter generates output voltage.

Freq.

MO

Run

command

13: During stop



Activated during stop.

Freq.

MO

Run

command

14: During constant run



Activated during nominal operation.

Freq.

MO

Run

command

15: During speed searching



Refer to Page 10-12 Speed search operation.

16: Wait time for run signal input



This function becomes active during normal operation and that the inverter waits for

active run command from external sequence.

17: Fault relay output



The parameter set in I56 is activated.



For example, if setting I55, I56 to 17 and 2, respectively, Multi-function output relay

will become active when trip other than “Low voltage trip” occurred.