Chapter 12. Protective functions

12.1 Electronic Thermal

Group

LED
display

Parameter Name

Set
value

Min/Max
setting

Factory
default

Unit

F50

[Electronic thermal
select]

1

0/1 0

F51

[Electronic thermal level for
1 minute]

- 150

%

F52

[Electronic thermal level for
continuous]

-

50/150

100 %

Function
group 1

F53

[Motor type]

- 0/1

0

ƒ Select F50 – [Electronic thermal select] to 1.

ƒ It activates when the motor is overheated (time-inverse). If current greater than set in F51 flows,

inverter output is turned off for the preset time in F51- [Electronic thermal level for 1 minute].



F51: Enter the value of max current that is capable of flowing to the motor continuously

for one minute. It is set in percent of motor rated current. The value cannot be set
lower than F52.



F52: Enter the amount of current for continuous operation. Normally motor rated

current is used. It cannot be set greater than F51.



F53: For an inductance motor, cooling effects decrease when a motor is running at low

speed. A special motor is a motor that uses a separately powered cooling fan
maximize cooling effect even in low speed. Therefore, as the motor speed changes,
the cooling does not change.

0

Standard motors having a cooling fan directly
connected to the shaft

F53 [Motor

type]

1

Special motor that uses a separately powered
cooling fan.








Current for

continuous [%]

100

95

65

20

60

Freq [Hz]

H53 = 1

H53 = 2

Current [%]

F51

F52

60

ETH trip time [sec]

110