Chapter 12. Protective functions

12.2 Overload Warning and trip


z Overload

warning

Group

LED
Display

Parameter Name

Set
value

Min/Max
setting

Factory
default

Unit

F54

[Overload warning
level]

-

30/150 150

%

Function
group 1

F55

[Overload warning time] -

0/30 10

Sec

I54

[Multi-function output
terminal select]

5

12

I/O group

I55

[Multi-function relay
select]

5

0/17

17

ƒ Select one output terminal for this function between MO and 30AC.
ƒ If selecting MO as output terminal, set I54 to 5 {Overload: OL}.



F54: Set the value as a percent of motor rated current.
















Current

Multi-function

output

F54

t : Overload

warning time

t

t

z Overload

trip

Group

LED
Display

Parameter Name

Set
value

Min/Max
setting

Factory
default

Unit

F56

[Overload trip select]

1

0/1 0

F57

[Overload trip level]

- 30/200

180 %

Function
group 1

F58

[Overload trip time]

- 0/60 60

sec

ƒ Set F56 to 1.
ƒ Inverter output is turned off when motor is overloaded.
ƒ Inverter output is turned off when excessive current flows to the motor for F58 – [Overload trip

time].