Chapter 12. Protective functions

12.3 Stall prevention

Group

LED
Display

Parameter Name

Set
value

Min/Max
setting

Factory
default

Unit

F59

[Stall prevention select]

-

0/7 3

Function
group 1

F60

[Stall prevention level]

-

30/150 150

%

I54

[Multi-function output
terminal select]

7 12

I/O group

I55

[Multi-function relay
select]

7

0/17

17

ƒ During acceleration: Motor acceleration is stopped when current exceeding the value set in F60

flows.

ƒ During constant run: Motor decelerates when current exceeding the value set in F60 flows.
ƒ During deceleration: Motor deceleration is stopped when inverter DC link voltage rises above a

certain voltage level.

ƒ F60: The value is set as the percent of motor rated current (H33).
ƒ I54, I55: Inverter outputs signals through multi-function output terminal (MO) or relay output (30AC)

when stall prevention function is activated. Stall prevention operation can be monitored by external
sequence.




F59: Stall prevention can be set as the table below.

During
Deceleration

During
constant
speed

During
Acceleration

Setting

Bit 2

Bit 1

Bit 0

0

- - -

1 -

-

9

2 -

9

-

3 -

9

9

4

9

- -

5

9

-

9

6

9

9

-

F59 [Stall

prevention
select]

7

9

9

9





For example, set F59 to 3 to make stall prevention active during Acceleration

and constant run.



When stall prevention is executed during acceleration or deceleration,

Accel/Decel time may take longer than the user-setting time.



When stall prevention is activated during constant run, t1, t2 executed in

accordance with the value set in ACC - [Accel time] and dEC - [Decel time].




112