12.5 External trip signal

Group

LED
display

Description

Set
Value

Min/Max
setting

Factory
default

Unit

I20

[Multi-function input
terminal P1 define]

0

~ ~

I23

[Multi-function input
terminal P4 define]

18

3

I/O group

I24

[Multi-function input
terminal P5 define]

19

0/24

4

ƒ Select a terminal among P1 thru P5 to output external trip signal.
ƒ Set I23 and I24 to 18 and 19 to define P4 and P5 as External A contact and B contact.



External trip signal input A contact (N.O): This is a normally open contact input. When

a P4 terminal set to “Ext trip-A” is ON, inverter displays the fault and turns off its output.



External trip signal input B contact (N.C): This is a normally closed contact input. When

a terminal set to “Ext trip-B” is OFF, inverter displays the fault and turns off its output.







P1

P4

P5

FX : I20 = 0

N.O. : I23 = 18

CM

N.C. : I24 = 19

P4(A contact)