Chapter 12. Protective functions

12.6 Inverter Overload



Inverter overload prevention function is activated when the current above inverter rated

current flows.



Multi-function output terminal (MO) or Multi-function relay (30AC) is used as the alarm

signal output during inverter overload trip.

Group

LED
display

Parameter Name

Set
value

Min/Max
Range

Factory
default

Unit

I54

[Multi-function output
terminal select]

7 12

I/O group

I55

[Multi-function relay
select]

7

0/17

17




12.7 Frequency command loss

Group

LED
display

Parameter Name

Set
value

Min/Max
setting

Factory
default

Unit

I16

[Criteria for analog
input signal loss]

0

0/2 0

I62

[Drive mode select after
loss of frequency
command]

-

0/2 0

I63

[Wait time after loss of
frequency command]

-

1.0 Sec

I54

[Multi-function output
terminal select]

11 12

I/O group

I55

[Multi-function relay
select]

11


1/12
0/17

17

ƒ Select the Drive mode when frequency reference set via V1 and I or (V1+I) input terminal or

communication option is lost.




I16: This is to set the criteria for analog input signal loss when frequency reference is given by V1,
I, V 1+I or Communication option.

0

Disabled (Does not check the analog input signal loss)

1

When less than the value set in I 2, I 7, I 12 is entered

I16

[Criteria for analog
input signal loss]

2

When below the value set in I 2, I 7, I 12 is entered


EX 1) The inverter determines that the freq reference is lost when DRV- Frq is set to 3 (Analog V1
input), I 16 to 1 and analog input signal is less than half of the minimum value set in I 7.

EX 2) The inverter determines that the freq reference is lost when DRV- Frq is set to 6 (V1+I), I 16
to 2 and V1 input signal is either below the minimum value set in I 7 or I input value is less than the
I 12 value.